SWA Series

SWA150 Standard Specifications

Item Capacity 150W
Model Name SWA150-05 SWA150-12 SWA150-15 SWA150-24
Input Rated Input Voltage AC100 - 240V
Input Voltage Range AC85 ~ 264V
Frequency Range 47 to 63Hz (rated frequency 50/60Hz)
Input Current Rated input/
output
conditions
2.4/1.2A(typ)
Inrush Current
(see Note 1)
Rated input/
output
conditions
20/40A (max)
Efficiency (typ) Rated input/
output
conditions
75% 77% 78% 79%
Power Factor (typ) Rated input/
output
conditions
0.99/0.95
Output
(see Note3)
Rated Output Voltage 5V 12V 15V 24V
Output Voltage Variation Rated output voltage±10%
Rated Output Current 30A 13A 10A 6.5A
Output Current Range 0~100%
Rated Output Power 150W 156W 150W 156W
Ripple Noise (mVp-p)
(see Note 2)
Rated input/
output conditions
120 180 180 240
Constant
Voltage
Accuracy
Static
Input Range
AC85~264V ±3%
Static
Load Range
0~100%
Time Drift 10min~8hour
Ambient
Temperature
Range
0~+50°C
Others Output Holdup Time Rated input/
output conditions
20ms(min)
Startup Time Rated input/
output conditions
1000/600ms(typ)
Leakage Current Rated input/
output conditions
0.5mA (Vin=100VAC)/0.75mA (Vin=240VAC)
Additional Functions Over Current Protection Detection above 120% of rated current
Over Voltage Protection Detection from 115% to 145% of rated voltage
(output cutoff)
Remote Sensing Provided
Remote On/Off Control Not provided
Display Red LED operation indicator
Environmental
Conditions
Operating Temperature Range 0 to +50°C (without cover)
Storage Temperature Range -25 ~ +85°C
Operating Humidity Range 30% to 90% (no condensation)
Storage Humidity Range 30% to 90% (no condensation)
Insulation Insulation Withstand Voltage (leakage current: 15mA or less) Between Input
and Output,
Between Input
and Frame
2,000V AC for 1 minute
Between
Output
and Frame
500V AC for 1 minute
Insulation resistance Between Input
and Output,
Between Input
and Frame,
Between
Output and
Frame
Above 100MW (measured with 500V DC Megger)
Structure Vibration Resistance 10 to 55Hz, 2G, 1 hour
(vibration in X, Y, Z directions, for 3 minutes) with horizontal mounting
Cooling Requirements Natural air cooling
External Appearance Open frame (cover and connector are optional)
External Dimensions (mm) 65W´200D´93H
Weight (g) 950
Applicable
Standards
Safety Standards UL 1950, CSA C22.2 No. 234, TUV (EN60950) certified
Conducted Emission Designed to meet VDE0871 Class A (200-240V AC)
Designed to meet FCC Class A (100-120V AC)

Note 1: At cold start. (More current may flow at restart.)
Note 2: Ripple noise is measured with a 100MHz oscilloscope using a 1:1 probe.
Note 3: All output characteristics are measured at the output connector.
* Rated input/output conditions means that the switching power supply is operated within the rated input voltage, rated output voltage, rated output current, and rated frequency, at an ambient temperature of 25°C and 60% humidity.
Top of page