| Item | Capacity | 100W | ||||||
|---|---|---|---|---|---|---|---|---|
| Model Name | SSH100-05 | SSH100-12 | SSH100-24 | |||||
| Input | Rated Input Voltage | AC100V/AC120V | ||||||
| Input Voltage Range | AC85~132V | |||||||
| Frequency Range | 47 to 440Hz (rated frequency: 50/60Hz) | |||||||
| Input Current | Rated input/ output conditions |
2.0A/1.8A(typ) | ||||||
| Inrush Current (see Note 1) |
Rated input/ output conditions | 30A(max) | ||||||
| Efficiency (typ) | Rated input/ output conditions |
82% | 87% | 90% | ||||
| Output (see Note3) |
Rated Output Voltage | 5V | 12V | 24V | ||||
| Output Voltage Variation | Rated output voltage±10% | |||||||
| Rated Output Current | 20A (18A)see Note 4 |
8.5A | 4.5A | |||||
| Output Current Range | 0~100% | |||||||
| Rated Output Power | 100W | 102W | 108W | |||||
| Ripple Noise (mVp-p) (see Note 2) |
Rated input/ output conditions |
80 | 100 | 100 | ||||
| Constant Voltage Accuracy |
Static Input Range |
AC85~132V | ±3% | |||||
| Static Load Range |
0~100% | |||||||
| Time Drift | 10min~8hour | |||||||
| Ambient Temperature Range |
0~+60°C | |||||||
| Others | Output Holdup Time | Rated input/ output conditions |
16ms(min) | |||||
| Startup Time | Rated input/ output conditions |
280ms(typ) | ||||||
| Leakage Current | Rated input/ output conditions |
0.3mA | ||||||
| Switching method, transformer frequency | SMZ method, approx. 70KHz | |||||||
| Additional Functions | Over Current Protection | Detection above 105% of rated current (output cutoff) | ||||||
| Over Voltage Protection | Detection above 115% of rated voltage (output cutoff) | |||||||
| Remote Sensing | Provided | |||||||
| Remote On/Off Control | Not provided | |||||||
| Display | Red LED operation indicator | |||||||
| Environmental Conditions |
Operating Temperature Range(see Note 5) | 0~+60°C | ||||||
| Storage Temperature Range | -25~+85°C | |||||||
| Operating Humidity Range | 30% to 90% (no condensation) | |||||||
| Storage Humidity Range | 30% to 90% (no condensation) | |||||||
| Insulation | Insulation Withstand Voltage (at normal temperature and humidity) |
Between Input and Output, Between Input and Frame |
2,000V AC for 1 minute (leakage current 15mA) | |||||
| Between Output and Frame |
500V AC for 1 minute (leakage current 15mA) | |||||||
| Insulation Resistance (at normal temperature and humidity) |
Between Input and Output, Between Input and Frame, Between Output and Frame |
100MW (measured with 500V DC Megger) | ||||||
| Structure | Vibration Resistance | 10 to 55Hz, 2G, 1 hour, (vibration in X, Y, Z directions, for 3 minutes)(with horizontal mounting) | ||||||
| Cooling Requirements | Natural air cooling | |||||||
| External Appearance | Open frame (cover is optional) | |||||||
| External Dimensions (mm) | 135x 93x 33(W x D x H) (without cover) | |||||||
| Weight (g) | Approx. 420 (without cover) | |||||||
| Applicable Standards |
Safety Standards |
|
||||||
| Conducted Emission | Designed to meet FCC Class B | |||||||
| Note 1: | At cold start. (More current may flow at restart.) |
| Note 2: | Ripple noise is measured with a 100MHz oscilloscope using a 1:1 probe. |
| Note 3: | Output characteristics are measured at the output connector. Ripple noise is measured at a point 5cm from the output connector, with a 63V 47µF electrolytic capacitor attached at that point. |
| Note 4: | It may be necessary to derate the output current depending on the operating conditions. Refer to the derated output current for the installation conditions and ambient temperature. |
| * | Rated input/output conditions means that the switching power supply is operated within the rated input voltage, rated output voltage, rated output current, and rated frequency, at an ambient temperature of 25°C and 60% humidity. |