SLS Series
SLS150 Standard Specifications
| Item | Capacity | 150W | |
|---|---|---|---|
| Model Name | SLS150PW | ||
| Input | Rated Input Voltage | AC100-120V/AC200-240V | |
| Input Voltage Range | AC85~132V/AC170~264V | ||
| Frequency Range | 47 to 63Hz (rated frequency 50/60Hz) | ||
| Input Current | Rated input/ output conditions |
4.2A(typ) | |
| Inrush Current (see Note 1) |
Rated input/ output conditions |
20/50A(max) | |
| Efficiency (typ) | Rated input/ output conditions |
80% | |
| Output (see Note3) |
Rated Output Voltage | 24V | |
| Output Voltage Variation | Fixed | ||
| Rated Output Current | 6A | ||
| Output Current Range | 0.1 to 15A (peak: 15A within 15 seconds) | ||
| Rated Output Power | 144W | ||
| Ripple Noise (mVp-p) | Rated input/ output conditions |
400 | |
| Constant Voltage Accuracy (see Note 2) | ±5% (typ) | ||
| Others | Output Holdup Time | Rated input/ output conditions |
20ms (typ) |
| Leakage Current | Rated input/ output conditions |
0.5/0.75mA | |
| Additional Functions |
Over Current Protection | Detection above 105% of peak current (automatic recovery) | |
| Over Voltage Protection | 110~145% | ||
| Remote Sensing | Not provided | ||
| Remote On/Off Control (see Note 4) | Provided | ||
| Display | Not provided | ||
| Environmental Conditions |
Operating Temperature Range | 0~ +50°C | |
| Storage Temperature Range | -25~ +80°C | ||
| Operating Humidity Range | 30% to 90% (no condensation) | ||
| Storage Humidity Range | 30% to 90% (no condensation) | ||
| Insulation | Insulation Withstand Voltage (at normal temperature and humidity) |
Between Input and Output, Between Input and Frame |
1,500V AC for 1 minute |
| Between Output and Frame |
500V AC for 1 minute or 600V AC for 1 second | ||
| Insulation Resistance (at normal temperature and humidity) |
Between Input and Output, Between Input and Frame, Between Output and Frame |
Above 100MW (measured with 500V DC Megger) |
|
| Structure | Vibration Resistance | 10 to 55Hz, 2G (with horizontal mounting), 1 hour (with 3-minute vibration time) | |
| Shock Resistance | 10G (3 times each in the X, Y, Z directions) | ||
| Cooling Requirements | Natural air cooling | ||
| External Appearance | Open frame | ||
| External Dimensions (mm) | 220W´98D´52H | ||
| Weight (g) | Approx. 850 | ||
| Applicable Standards |
Safety Standards | UL 1950, CSA No. 234, TUV (EN60950) certified | |
| Conducted Emission | Designed to meet FCC Class A and VCCI Class A | ||
| Note 1: | A higher inrush current than the value indicated may flow at restart. |
| Note 2: | The rated voltage accuracy is measured under the input voltage variable range of 85 to 132V AC, within the output current variable range, with a time drift of 10 minutes to eight hours and an ambient temperature range from 0 to +50°C. |
| Note 3: | Although the SLS060P has a thermal shutdown function to prevent overheating (SLS100P does not have this function), it is a simple system so the device must not be continuously operated when the output current exceeds the rated current. |
| Note 4: | The maximum rated values for the remote ON/OFF control pins (pins 1 & 2 of CN2) are 15V and 15mA. |
| * | Measurements are made at a point 5cm from the output terminal for all output characteristics, with a 63V 47µF electrolytic capacitor attached at that point. (A 1:1 probe is used.) |
| * | Rated input/output conditions means that the switching power supply is operated within the rated input voltage, rated output voltage, rated output current, and rated frequency, at an ambient temperature of 25°C and 60% humidity. |