SAMCO-vm05 Series (SHF/SPF, SBT)

200V system (SBT model)

200V system (SBT model)

Model SBT-30K SBT-37K SBT-45K SBT-55K
Load*1 H characteristic
Output Applicable motor capacity 30 kW 37 kW 45 kW 55 kW
Rated capacity*2 43.8 kVA 55.2 kVA 68.5 kVA 83.8 kVA
Rated current*3 115 A 145 A 180 A 220 A
Overload current rating*4 172 A 217 A 270 A 330 A
Rated output voltage 200 V 50/60 Hz, 220 V 60 Hz
Input Rated voltage and frequency 3φ 200 to 230 V, 50/60 Hz
Allowable fluctuation Voltage: ±10%, Frequency: ±5%, Voltage imbalance: 3% max.
Power supply impedance 1% or more (Use the optional reactor if less than 1%)
Protective structure Totally enclosed (IP20)
Cooling method Forced air cooling
Gross weight 32 kg 38 kg
Control functions Control method V/f control or sensorless vector control
High-frequency carrier Sine wave PWM (carrier frequency: 1 to 10 kHz)*5
Output frequency range 0.05 to 600 Hz (starting frequency: 0.05 to 20 Hz variable)*6
Frequency
setting
resolution
Digital setting 0.01 Hz (0.05 to 600 Hz)
Analog setting 10 bits for 0 to 10 V, 4 to 20 mA, 9 bits for 0 to 5 V for maximum output frequency
Frequency
accuracy
Digital setting ±0.01% of the output frequency (at -10 to +40°C)
Analog setting ±0.2% of the maximum output frequency (at 25°C ±10°C)*7
DC braking Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Additional functions Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump,
auto alarm recovery, PID control operation, simple scheduled operation, energy-saving operation,
torque limiter (for sensorless vector control only)
Operational functions Start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminals
Frequency
command
setting
Digital setting Operation panel, serial communication (RS485, RS232C), step setting from terminal board
Analog setting 2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA, variable resistor (5 kΩ, 0.3 W or more)
Input signals Frequency command, forward run command, reverse run command, acceleration/deceleration time setting,
free-run stop/alarm reset, emergency stop, jogging selection,
step frequency setting, operation signal hold, torque limiter (sensorless vector control only)
[Digital input: 8 channels (arbitrary allocation available)] [Analog input: 1 channel for voltage, 1 channel for current and voltage]
Output
signals
Contact output Alarm batch and multifunctional contact output (1C contact, 250VAC, 0.3 A)
Monitor signal Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach,
[Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels]
LED display Frequency, output current, synchronous rotation, load factor, output voltage,
pressure, line speed (no units), operating, alarm
Serial communication I/F RS485, RS232C
Function extension Software upgrade by RS232C serial communication supported
External power supply output 24 VDC, 150 mA (control terminal)
Protection functions Current limiting, overcurrent shutoff, motor overload, external thermal alarm,
undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning functions Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat,
overload, overheating of radiator fins
Environment Ambient temperature -10 to +50°C (However, remove top ventilation cover at +40°C and higher)
Storage temperature -20 to +65°C*8
Ambient humidity 90% or less (with no condensation)
Operating environment Indoors at 1,000 m or lower altitude
(No direct sunlight, corrosive or inflammable gases, oil mist, or dust)
  • *1 H characteristic: Constant torque load (for general industry)
  • *2 Rated capacity at the output voltage of 220 V
  • *3 When the input voltage is 200 V or above, rated current will be decreased according to the output power.
  • *4 1 minute every 10 minutes
  • *5 The maximum carrier frequency varies with the rated characteristics and the operating status.
  • *6 The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
  • *7 The maximum output frequency is at 5 V, 10 V, and 20 mA.
  • *8 This temperature is for short periods, such as during transportation.