SAMCO-vm05 Series (SHF/SPF, SBT)
200 V type (SBT model) 1
200 V type (SBT model) 1,2 | 400 V type (SHF model) 1,2 | 400 V type (SPF model) 1,2
| Model | SBT- 0.75K /1.5K |
SBT- 1.5K /2.2K |
SBT- 2.2K /3.7K |
SBT- 3.7K /5.5K |
SBT- 5.5K /7.5K |
SBT- 7.5K /11K |
SBT- 11K /15K |
SBT- 15K /18.5K |
SBT- 18.5K /22K |
SBT- 22K /30K |
||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output | Load*1 | H | P | H | P | H | P | H | P | H | P | H | P | H | P | H | P | H | P | H | P | |
| Applicable motor capacity [kW] |
0.75 | 1.5 | 1.5 | 2.2 | 2.2 | 3.7 | 3.7 | 5.5 | 5.5 | 7.5 | 7.5 | 11 | 11 | 15 | 15 | 18.5 | 18.5 | 22 | 22 | 30 | ||
| Rated capacity [kVA]*2 |
1.9 | 2.7 | 3.0 | 3.7 | 4.3 | 5.8 | 6.7 | 8.5 | 9.1 | 11.4 | 12.8 | 16.8 | 17.5 | 21.7 | 22.9 | 25.9 | 28.6 | 31.2 | 33.5 | 41.9 | ||
| Rated current [A] |
5.1 | 7.0 | 8.0 | 9.6 | 11.2 | 15.1 | 17.6 | 22.3 | 24 | 30 | 33 | 44 | 46 | 57 | 60 | 68 | 75 | 82 | 88 | 110 | ||
| Overload current [A]*3 |
7.6 | 8.4 | 12.0 | 11.5 | 16.8 | 18.1 | 26.4 | 26.7 | 36 | 36 | 49.5 | 52.8 | 69 | 68.4 | 90 | 81.6 | 112.5 | 98.4 | 132 | 132 | ||
| Input | Rated output voltage |
200V 50/60Hz 220V 60Hz | ||||||||||||||||||||
| Rated voltage and frequency |
3φ 200V to 230V 50/60Hz | |||||||||||||||||||||
| Allowable fluctuation |
Voltage: ±10%, frequency: ±5%, voltage imbalance: 3% max. |
|||||||||||||||||||||
| Source impedance |
1% or more (Use the optional reactor if less than 1%) | |||||||||||||||||||||
| Protective structure |
Shutdown method (IP20) | |||||||||||||||||||||
| Cooling method |
Self-cooling | Forced air cooling | ||||||||||||||||||||
| Gross weight |
3kg | 4kg | 4kg | 4.5kg | 8kg | 8kg | 10kg | 12kg | 15kg | 18kg | ||||||||||||
| Control functions |
Control method |
V/f control or sensorless vector control | ||||||||||||||||||||
| High-frequency carrier |
Sine wave PWM (carrier frequency: 1 to 14 kHz)*4 | |||||||||||||||||||||
| Output frequency range |
H | 0.05 to 600 Hz (starting frequency: 0.05 to 20 Hz, variable)*5 | ||||||||||||||||||||
| P | 0.01Hz (0.05 to 600Hz) | |||||||||||||||||||||
| Frequency setting resolution |
Digital setting |
0.01 Hz (0.05 to 600 Hz) | ||||||||||||||||||||
| Analog setting |
0.1% (10 bits for 0 to 10 V, 4 to 20 mA), 0.2% (9 bits for 0 to 5 V) for maximum output frequency | |||||||||||||||||||||
| Frequency accuracy |
Digital setting |
±0.01% of output frequency (at 10 to 40°C) | ||||||||||||||||||||
| Analog setting |
±0.2% of maximum output frequency (at 25°C ±10°C)*6 | |||||||||||||||||||||
| DC braking | Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps) | |||||||||||||||||||||
| Additional functions |
Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump, auto alarm recovery, PID control operation, simple scheduled operation, energy-saving operation, torque limiter (for sensorless vector control only) |
|||||||||||||||||||||
| Operational functions |
Start/ stop setting |
Operation panel, serial communication (RS485, RS232C), control circuit terminals | ||||||||||||||||||||
| Frequency command setting |
Digital setting |
Operation panel, serial communication (RS485, RS232C), step setting from terminal board | ||||||||||||||||||||
| Analog setting |
2 external channels: 0 to 5 V, 0 to 10 V, 4 to 20 mA, external variable resistor (5 kΩ , 0.3 W or higher) | |||||||||||||||||||||
| Input signals |
Frequency command, forward run command, reverse run command, acceleration/ deceleration time setting, free-run stop/ alarm reset, emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only), (Digital input: 8 channels (arbitrary allocation available)) (Analog input: 1 channel for current and voltage) |
|||||||||||||||||||||
| Output signals |
Contact output |
Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A) | ||||||||||||||||||||
| Monitor signals |
Operating, frequency matching, overload alarm, undervoltage, frequency approach (Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels) |
|||||||||||||||||||||
| LED display |
Frequency, output current, number of synchronous rotations, load factor, output voltage, pressure, line speed (no units), operating, alarm | |||||||||||||||||||||
| Serial communication I/F |
RS485, RS232C | |||||||||||||||||||||
| Function extension |
Software upgrade via RS232C serial communication supported | |||||||||||||||||||||
| External power supply output |
24 VDC, 150 mA (control terminal board) | |||||||||||||||||||||
| Protection functions |
Current limiting, overcurrent shutoff, motor overload, external temperature, undervoltage, overvoltage, momentary power failure, fin overheat, open phase |
|||||||||||||||||||||
| Warning functions |
Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins | |||||||||||||||||||||
| Environment | Ambient temperature |
H | -10 to +50°C (Top ventilation cover to be removed at +40°C and higher) | |||||||||||||||||||
| P | 10 to +40°C (Top ventilation cover to be removed at +30°C and higher for SBT-3.7K/5.5K and earlier models) | |||||||||||||||||||||
| Storage temperature |
-20 to +65°C*7 | |||||||||||||||||||||
| Relative humidity |
90% or less (with no condensation) | |||||||||||||||||||||
| Operating environment |
Indoors at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust) |
|||||||||||||||||||||
- H: H characteristic - Constant torque load (for general industry),
P: P characteristic - Dual law decreasing torque load (for fans and pumps) - Rated capacity at an output voltage of 220 V
- 1 minute every 10 minutes
- The maximum carrier frequency varies depending on the rated characteristics and the operating status.
- The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
- The maximum output frequency is at 5 V, 10 V, and 20 mA.
- This temperature is for short periods, such as during transportation.
- The SBT-7.5K/11K and earlier models are equipped with discharge resistors as standard.