SAMCO-vm05 Series (SHF/SPF, SBT)

Software Functions

Control algorithms for various types of applications are provided as standard, and through the provision of software customized to customer requirements, each inverter can be used as a dedicated inverter that precisely meets system needs.

Function Applications Purpose Description
Rating selection
function
SBT, general industry Selection of optimal rating In the 200 V type SBT series, 150%/minute for the H mode and 120%/minute for the P mode can be selected based on the overload capacity. Select the rating according to the motor capacity and load status.
Upgrade function Special applications Function expansion Control software can be upgraded according to special applications and requests.
Communication
function
General industry Centralized monitoring control RS-232C and RS-485 serial communication functions are provided as standard.
Frequency setting General industry Frequency range extension A wide output frequency range from 0.05 to 600 Hz can be set (V/f mode).
Terminal board
step setting
General industry Digital frequency setting from
remote location
The frequency can be gradually raised and lowered with the up and down control input terminals.
Multifunctional
input terminal
General industry Multi-functionalization of
terminal board input function
The contact input terminals for 8 channels can be allocated to
multiple multifunctional input terminals.
Multifunctional
output terminal
General industry Multi-functionalization of
terminal board output function
The open collector output terminals for 3 channels can be allocated to multiple multifunctional output terminals.
Multifunctional
relay output
General industry Multi-functionalization of
relay output
Relay output of various statuses, in addition to during alarms can be performed.
Analog output General industry Monitor and sequential
operation
Two channels of analog output of 0 to 10 V are provided, enabling the selection of frequency, current, voltage, and other data.
Frequency
counter output
General industry Frequency connection with
upper-level controller
Counter outputs proportional to the inverter output frequency can be output up to 10 times to any 3-channel open-collector output terminal.
Analog input General industry Loading of command
value and feedback values
Command values such as frequency and pressure, and various feedback signals can be input with analog signals of 0 to 5 V, 10 V, and 4 to 20 mA.
Analog input
filter
General industry Reduction of peripheral
devices
A power supply of 24 VDC, 150 mA max. can be provided to external peripheral devices.
User-supplied
power supply
General industry Reduction of peripheral
devices
A power supply of 24 VDC, 150 mA max. can be provided to external peripheral devices.
User default
function
General industry Improvement of operability and
maintainability
The setting value of the status following function code adjustment data verification can be saved as an initial value.
Changed data
display function
General industry Improvement of operability and
maintainability
The changed function code number and data contents can be displayed sequentially.
Copy function General industry Improvement of operability The current function code adjustment data can be copied via the operation panel.
Constant-time
inching function
Circular weaving machines, machine tools Improvement of position
accuracy
Even if the operation switch-on time differs according to the operator, constant-time operation is performed, for improved position accuracy. (Minimum operation time function)
I/O open-phase
detection function
General industry Improvement of
protection functions
Protection is performed by detecting open phases for inverter input and output. The availability of functions can also be selected.
V/f separation
function
Winders Free torque control The inverter output frequency and voltage can be freely changed and the V/f ratio type and complete separation type can be selected for the load.
Free V/f pattern Lifts, elevators Free torque control In addition to linear V/f patterns, two intermediate points can be freely set.
Cooling fan lock detection Small-capacity machines,
general
Improvement of
protection functions
Protection is performed for small-capacity equipment by detecting the cooling fan lock status. Moreover, the availability of on/off control for the cooling fan can be selected.
Set frequency
gain function
Winders Fine adjustments of
sequential operation
To perform sequential operation of multiple inverters, the interlocking ratio of each inverter can be adjusted, for example, with a variable resistor.
Energy saving
control
Air conditioning, pumps Maximum efficiency
operation
Energy-saving operation that maximizes motor efficiency is performed using the energy-saving function, V/f automatic energy-saving function, sensorless vector control automatic energy saving function.
PID control operation Air conditioning, pumps Automatic process
control
Automatic process control according to various control factors such as speed, flow amount, and pressure is enabled through PID control.
PID, V/f
switch operation
Air conditioning, pumps Automatic/
manual switching
Feedback control through PID and open loop control with V/f constant control can be switched with a control terminal input signal. This is effective for switching during production and adjustments, and during preparations.
Vector, V/f
switch operation
Conveyers Operation mode
switching
Sensorless vector control and V/f constant control can be switched with the control terminal input signal. This is effective for switching during production and adjustments, and during preparations.
Multi-speed operation General industry Variable speed Depending on the combination of control input terminals, variable speed operation of up to 8 different speeds is possible.
Acceleration-deceleration switc
h operation
General industry Variable acceleration/
deceleration time
Depending on the combination of control input terminals, the acceleration/deceleration time toward the set frequency can be switched between up to 4 levels.
Figure S acceleration/
deceleration operation
Lifts, elevators Shock-less acceleration/
deceleration
The speed at acceleration/deceleration start, intermediate time, and acceleration/deceleration end can be freely adjusted with a curve (figure S). This function is ideal for shock-less operation, such as for elevators and conveyor belts.
Operation signal
hold function
General industry Operation with one-shot
connection signal
Continuous operation is possible even if using operation signal contacts by using, for example, a one-shot momentary switch.
Simple scheduled
operation
General industry Scheduled operation
following the set pattern
Scheduled operation is performed with up to 7 patterns for which frequency, time, acceleration/deceleration time, operation direction, etc., have been set in advance.
Disturbed
operation
Spinning machinery Variable speed according
to bobbin diameter
Alternate operation is performed during the setting time for high-speed frequency and low-speed frequency. Modulation can be added to the high and low frequencies. It is suitable for the easy bobbin winding of weaving machines.
Carrier
frequency
General industry Noise reduction The inverter output switching carrier frequency can be freely adjusted. This function is effective for reducing motor noise and other mechanical noises, as well as leak current.
Unstable
phenomena removal function
Extruding machines and the like Current ripple elimination This function reduces output current instability that tends to occur in the case of low frequency or light load.
Monitor display General industry Status monitoring This function displays the frequency, current, voltage, load factor, etc., on the operation panel LEDs. Moreover, when no unit display is selected, statuses such as feedback frequency, fin temperature, and direct current voltage, can be displayed.
Current control
function
General industry Improvement of
protection functions
This function automatically performs acceleration in the optimum acceleration time in order to reduce the overcurrent during inverter acceleration to the set value.
Overvoltage stall prevention function Machine tools Improvement of
protection functions
This function automatically adjusts the deceleration curve to reduce the regeneration voltage during inverter deceleration. Function availability can also be selected.
Momentary power
failure restart function
Air conditioning, pumps Trip-less operation Following power recovery after a momentary power failure, shock-less restart is automatically performed through a scooping-up operation.
Momentary drop
compensation function
Winders, inertial load Trip-less operation Using this function, the inverter is placed in the regeneration status through deceleration, the chronic energy on the load side is effectively used, and the time until a trip is considerably lengthened, in order to suppress undervoltage trips upon occurrence of a momentary power failure.
Scooping-up
operation
Fans, inertial load Trip-less operation Even when the inverter operation command is set to on with the motor in the freewheel-spinning status, the number of motor rotations and the rotation direction are detected, and shock-less start is performed from the current rotating speed. If the rotation direction differs from the command, deceleration is performed after scooping-up, and acceleration is performed again in the command direction.
Auto alarm
recovery function
Air conditioning, pumps Trip-less operation Even if the inverter stops abnormally, the inverter starts again automatically following analysis of the abnormality. Upon restart, scooping-up operation is performed for shock-less operation.
Alarm details
readout
General industry Anomaly analysis The inverter alarm stop history is saved for up to five occurrences. Anomaly analysis can be done from the operation panel.
Constant pressure
feedwater system
control
Pumps Constant feedwater
pressure control for
multiple pumps
A constant pressure feedwater system combining multiple pumps can be built by installing an SWS option board. A periodic switching function for extending pump life, and a pump selection function provided through control terminals whose maintainability has been improved, are provided.
Winding
control
Winders Constant tension, wide
speed range winder,
feeding control
Control of winders, feeders, rewinders, etc., supporting a wide range of line speeds for a constant tension is possible without a dedicated controller, through dedicated winding patterns and a dedicated dancer correction control function.
Position
control
Machine tools Point-to-point control,
continuous path control
Speed control and position control are enabled by mounting the SB-PG option board and performing feedback of the speed detected by the PG speed sensor. In the case of position control, by directly setting the travel distance from the operation panel, point-to-point control is enabled even when there is no command pulse.
Current output
function
General industry Current monitoring,
sequential operation
By mounting the SAS option board, current output proportional to inverter output frequency is performed with 4 to 20 mA. A gain of up to 20 times can be set.