SAMCO-vm05 Series (SHF/SPF, SBT)
Function Codes
| Code No. Cd |
Function | Data | Setting resolution | Factory Setting | User’s Setting |
|---|---|---|---|---|---|
| 000 | Display selection | 1: Frequency (Hz) 2: Output current 3: Speed of rotation (rpm) 4: Load factor 5: Output voltage 6: Pressure value 7: No units display |
1 | 1 | |
| 001 | Operation command selection | 1: Operation panel 2: External terminal signal 3: Communication |
1 | 1 | |
| 002 | 1st speed frequency setting | 1: Operation panel 2: External analog VRF1 (0 - 5 V) 3: External analog VRF1 (0 - 10 V or variable resistor) 4: External analog VRF2 (0 - 5 V) 5: External analog VRF2 (0 - 10 V or variable resistor) 6: External analog IRF (4 - 20 mA) 7: External analog VRF1 + VRF2 8: External analog VRF1 - VRF2 9: External analog VRF2 - VRF1 10: External analog VRF1 + IRF 11: External analog VRF1 - IRF 12: External analog IRF - VRF1 13: Terminal board step 14: Communication 15: BINARY (option) 16: BCD (option) |
1 | 1 | |
| 003 | V/f pattern | 1: Linear pattern 1 1 2: Square-law decreasing pattern (weak) 3: Square-law decreasing pattern (strong) |
1 | 1 | |
| 004 | Torque boost | 0 - 20% (maximum voltage ratio) | 0.1% | *1 | |
| 005 | Base voltage | 200 V system 0: No AVR 30 - 240 V |
1V | *1 | |
| 400 V system: 0: No AVR 30 to 460 V | |||||
| 006 | Base frequency | 0.1 - 60 Hz | 0.01Hz | *1 | |
| 007 | Upper frequency limit | 30 - 600 Hz | 0.01Hz | 60 | |
| 008 | Lower frequency limit | 0.05 - 200 Hz | 0.01Hz | 0.05 | |
| 009 | Starting method | 1: Starting frequency 2: Flying start 3: Starting frequency after DC braking |
1 | 1 | |
| 010 | Starting frequency | 0.05 - 20 Hz | 0.01Hz | 1 | |
| 011 | Operation start frequency | 0 - 20 Hz | 0.01Hz | 0 | |
| 012 | Start delay time | 0 - 5 sec. | 0.1 s | 0 | |
| 013 | Braking method | 1: Deceleration to stop 1 1 2: Deceleration to stop + DC braking 3: Free run stop |
1 | 1 | |
| 014 | DC braking start frequency | 0.2 - 20 Hz | 0.01Hz | 0.5 | |
| 015 | DC braking time | 0.1 - 10 sec. | 0.1 s | 2 | |
| 016 | DC braking force | 1 - 10 | 1 | 5 | |
| 017 | Acceleration/deceleration curve | 1: Linear 2: S-shaped |
1 | 1 | |
| 018 | Reference acceleration/ deceleration frequency | 10 - 120 Hz | 0.01 Hz | *1 | |
| 019 | 1st acceleration time | 0 - 6500 sec. | 0.1 s | *2 | |
| 020 | 2nd acceleration time | 0 - 6500 sec. | 0.1 s | *3 | |
| 021 | 3rd acceleration time | 0 - 6500 sec. | 0.1 s | *4 | |
| 022 | 4th acceleration time | 0 - 6500 sec. | 0.1 s | *5 | |
| 023 | 1st deceleration time | 0 - 6500 sec. | 0.1 s | *6 | |
| 024 | 2nd deceleration time | 0 - 6500 sec. | 0.1 s | *7 | |
| 025 | 3rd deceleration time | 0 - 6500 sec. | 0.1 s | *8 | |
| 026 | 4th deceleration time | 0 - 6500 sec. | 0.1 s | *9 | |
| 027 | JOG acceleration/deceleration time | 0.1 - 60 Hz | 0.1 s | 0.1 | |
| 028 | Jog frequency | 0.1 - 60 Hz | 0.01Hz | 5 | |
| 029 | 1st speed frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 030 | 2nd speed frequency | 0 to 600 Hz | 0.01Hz | 10 | |
| 031 | 3rd speed frequency | 0 to 600 Hz | 0.01Hz | 20 | |
| 032 | 4th speed frequency | 0 to 600 Hz | 0.01Hz | 30 | |
| 033 | 5th speed frequency | 0 to 600 Hz | 0.01Hz | 40 | |
| 034 | 6th speed frequency | 0 to 600 Hz | 0.01Hz | 50 | |
| 035 | 7th speed frequency | 0 to 600 Hz | 0.01Hz | 60 | |
| 036 | 8th speed frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 037 | 1st Jump frequency lower limit | 0 to 600 Hz | 0.01Hz | 0 | |
| 038 | 1st jump top frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 039 | 2nd jump bottom frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 040 | 2nd jump top frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 041 | 3rd jump bottom frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 042 | 3rd jump top frequency | 0 to 600 Hz | 0.01Hz | 0 | |
| 043 | Output current limiting | H characteristic/SHF 0: No function 50 - 200% | 1% | 150 | |
| P characteristic/SPF 0: No function 50 - 150% | 1% | 120 | |||
| 044 | Electrothermal level setting | 0: No function 20 - 105% | 1% | 100 | |
| 045 | Output current limiting during constant power operation | 0: No 1: Yes V/F mode only (Currently selected acceleration/deceleration time) 2: Yes V/F mode only (Acceleration/Deceleration time = Cd019, Cd023: 1st acceleration/deceleration time) 3: Yes V/F mode only (Acceleration/Deceleration time = Cd020, Cd024: 2nd acceleration/deceleration time) 4: Yes V/F mode only (Acceleration/Deceleration time = Cd021, Cd025: 3rd acceleration/deceleration time) 5: Yes V/F mode only (Acceleration/Deceleration time = Cd022, Cd026: 4th acceleration/deceleration time) 6: Yes V/F mode and sensorless vector control mode (Acceleration/Deceleration time = Cd019, Cd023: 1st acceleration/deceleration time) 7: Yes V/F mode and sensorless vector control mode (Acceleration/Deceleration time = Cd020, Cd024: 2nd acceleration/deceleration time) 8: Yes V/F mode and sensorless vector control mode (Acceleration/Deceleration time = Cd021, Cd025: 3rd acceleration/deceleration time) 9: Yes V/F mode and sensorless vector control mode (Acceleration/Deceleration time = Cd022, Cd026: 4th acceleration/deceleration time) |
1 | 0 | |
| 046 | Restart after momentary power failure | 0: Do not restart. 1: Restart. 2: Compensation for momentary power failure |
1 | 0 | |
| 047 | Auto alarm recovery | 0: No auto alarm recovery function 1: Auto alarm recovery function |
1 | 0 | |
| 048 | Overload alarm level setting | H characteristic/SHF 20 - 200% | 1% | 150 | |
| P characteristic/SPF 20 - 150% | 1% | 120 | |||
| 049 | Duty cycle of brake resistor | 0: No brake resistor 2 - 25% ED 99: External brake unit |
1%ED | *1 | |
| 050 |
Direction of rotation of motor
Note: Cd130 for direction command |
1: Forward and reverse run 2: Forward run only 3: Reverse run only |
1 | 1 | |
| 051 | Carrier frequency | 0 - 130 | 1 | *1 | |
| 052 | Motor type | 1: General-purpose motor 2: Inverter dedicated motor |
1 | 1 | |
| 053 | Motor poles, voltage, and capacity | XYZZZ X: Number of motor poles Y: Rated voltage Z: Motor capacity |
- | *1 | |
| 054 | Bias frequency (VRF1) | 0 to ±600 Hz (frequency at 0 V) | 0.1Hz | P0 | |
| 055 | Gain frequency (VRF1) | 0 to ±600 Hz (frequency at 5 V or 10 V) | 0.1Hz | P60 | |
| 056 | Approach frequency | 0 - 600 Hz | 0.01Hz | 10 | |
| 057 | Frequency matching range | 0 - 10 Hz | 0.01Hz | 0 | |
| 058 | No-unit display amplification | 0 to 100 (amplification in relation to output frequency) |
× 0.01 | 1 | |
| 059 | Display selection | 1: No units (multiple of CD058) 2: PID feedback frequency [Hz] 3: Command pressure [MPa] (option) 4: Set pressure [MPa] (option) 5: Command frequency [Hz] 6: Fin temperature [°C] 7: Detecting speed [rpm] (option) 8: Regular pump switching integrated time [H] (option) 9 - 10: Reserved 11: Detecting position [mm] (option) 12: DC voltage [V] 13: Output power [kW] (V/f mode only) |
1 | 1 | |
| 060 | Rating selection Note: This function is for SBT series only. |
1: H characteristic (150% rating) 2: P characteristic (120% rating) |
1 | 1 | |
| 061 | Instability elimination | 0 - 20 | 1 | *1 | |
| 062 | Bias frequency (IRF/VRF2) | 0 to ± 600 Hz (frequency at 5 V or 10 V or 20 mA) | 0.1Hz | P0 | |
| 063 | Gain frequency (IRF/VRF2) | 0 to ±600 Hz (frequency at 5 V or 10 V or 20 mA) | 0.1Hz | P60 | |
| 064 | Discharge resistor on signal output time | 0.01 - 10 s | 0.01 s | 0.1 | |
| 065 | Set frequency gain | 0 - 100% | 1 | 0 | |
| 066 | V·f separate function selection | 1: V·f comparison 2: Complete separation |
1 | 1 | |
| 067 | MBS terminal input mode | 1: Level operation 2: Edge operation |
1 | 1 | |
| 068 | Internal analog output bias 1 | 0 - ±10.0 V | 0.1V | P0 | |
| 069 | Internal analog output bias 2 | 0 - ±10.0 V | 0.1V | P0 | |
| 070 | ES input terminal function | 1: NO external thermal signal 2: NC external thermal signal |
1 | 1 | |
| 071 | Motor control mode selection | 1: V/f control mode 2: Sensorless vector control mode 3: Internal PID control mode 4: Position control (optional) 5: Speed control (optional) 6: Simple energy-saving mode 7: Auto energy-saving mode 1 8: Auto energy-saving mode 2 9: Auto tuning mode 1 10: Auto tuning mode 2 11: V·f separate control 12: Switching between sensorless vector control and V/f control |
1 | 1 | |
| 072 | Torque limiter (power running) | H characteristic/SHF: 5 - 200% | 1% | 100 | |
| P characteristic/SPF: 5 - 150% | |||||
| 073 | Torque limiter (regeneration) | 5 - 100% | 1% | *1 | |
| 074 | Multiple for starting excitation current | 1 - 10 (for applicable motor) | 1 | 5 | |
| 075 | Striking excitation time | 0 - 10 (for no starting excitation) | 0.1 s | *1 | |
| 076 | Multiple for braking excitation current | 1 - 10 (for applicable motor) | 1 | 5 | |
| 077 | Braking excitation time | 0 - 10 (for no starting excitation) | 0.1 s | 1 | |
| 078 | Motor current rating | Approx. 30 - 110% of inverter current rating | 0.1A | *1 | |
| 079 | Motor frequency rating | 1: 50 Hz 2: 60 Hz |
1 | *1 | |
| 080 | Motor speed rating | 0 to 24000 rpm | 1rpm | *1 | |
| 081 | Motor isolation type | 1: Type A 2: Type E 3: Type B 4: Type F 5: Type H |
1 | *1 | |
| 082 | Speed adjustment gain | 0.5 to 2 | 0.01 | 1 | |
| 083 | External analog input filter time constant | 1 - 500 (set value: 1 = 10 ms) | 10ms | 10 | |
| 084 | Copy function | 1: Transfer the current code data to the
operation panel 2: Transfer the operation panel memory to the inverter |
1 | 0 | |
| 085 | Torque limiter analog input function (power running) | 0: Limit using Cd072 1: Limit using the signal on the VRF1 terminal (0 to 5 V) 2: Limit using the signal on the VRF1 terminal (0 to 10 V or variable resistor) 3: Limit using the signal on the VRF2 terminal (0 to 5 V) 4: Limit using the signal on the VRF2 terminal (0 to 10 V or variable resistor) 5: Limit using the signal on the IRF terminal (4 to 20 mA) |
1 | 0 | |
| 086 | Torque limiter analog input function (regeneration) | 0: Limit using Cd073 1: Limit using the signal on the VRF1 terminal (0 to 5 V) 2: Limit using the signal on the VRF1 terminal (0 to 10 V or variable resistor) 3: Limit using the signal on the VRF2 terminal (0 to 5 V) 4: Limit using the signal on the VRF2 terminal (0 to 10 V or variable resistor) 5: Limit using the signal on the IRF terminal (4 to 20 mA) |
1 | 0 | |
| 087 | Function to switch between “OV” and “LV” alarms when stopped | 0: OV enabled, LV disabled during stop 1: OV disabled, LV enabled during stop 2: OV disabled, LV disabled during stop 3: OV enabled, LV enabled during stop |
1 | 0 | |
| 088 | ASR proportional gain | 0 - 7.8 | 0.01 | *1 | |
| 089 | ASR integral gain | 0 - 106 | 0.01 | *1 | |
| 090 | Start of S-shaped acceleration | 0 - 100% | 1% | 50 | |
| 091 | End of S-shaped acceleration | 0 - 100% | 1% | 50 | |
| 092 | Gradient of middle of S-shaped acceleration | 0 - 100% | 1% | 0 | |
| 093 | Start of S-shaped deceleration | 0 - 100% | 1% | 50 | |
| 094 | End of S-shaped deceleration | 0 - 100% | 1% | 50 | |
| 095 | Gradient of middle of S-shaped deceleration | 0 - 100% | 1% | 0 | |
| 096 | Function lock | 0: Code data changeable (No lock function) 1:Code data unchangeable (except Cd096) 2:Code data unchangeable (except Cd096 and Cd028 to Cd036) 3: Code data unchangeable (except Cd096 or using communication function) 4: Code data unchangeable (except for Cd096, Cd175 or Cd182, pressure command.) |
1 | 0 | |
| 097 | Operation time display | Read only | 1 hour | --- | |
| 098 | Reading alarm data | 0 1: Read start 9: Record erase |
1 | 0 | |
| 099 | Data initialization | 0 1: Initialize factory presets 2: Invalid constant by auto tuning 3: Initialize user’s data 99:Set user’s initialization value |
1 | 0 | |
| 100 | Operation panel remote/local selection |
0 1: Toggle function (optional) |
1 | 0 | |
| 101 | Operation mode selection | 0: Normal operation 1: Simple scheduled operation 2: Disturbed operation |
1 | 0 | |
| 102 | Simple scheduled operation repetition |
0: Continuous 1 - 250: Repetition count |
1 | 1 | |
| 103 | Operation timer T1 | 0 - 6500 s | 1 s | 10 | |
| 104 | Operation timer T2 | 0 - 6500 s | 1 s | 10 | |
| 105 | Operation timer T3 | 0 - 6500 s | 1 s | 10 | |
| 106 | Operation timer T4 | 0 - 6500 s | 1 s | 10 | |
| 107 | Operation timer T5 | 0 - 6500 s | 1 s | 10 | |
| 108 | Operation timer T6 | 0 - 6500 s | 1 s | 10 | |
| 109 | Operation timer T7 | 0 - 6500 s | 1 s | 10 | |
| 110 | Operation stop timer T0 | 0 - 6500 s | 1 s | 10 | |
| 111 | Midway stop deceleration time | 1 - 4: Data of Cd023 - Cd026 | 1 | 1 | |
| 112 | Midway start acceleration time | 1 - 4: Data of Cd019 - Cd022 | 1 | 1 | |
| 113 114 115 116 117 118 119 |
Forward/reverse and acceleration/deceleration in T1 Forward/reverse and acceleration/deceleration in T2 Forward/reverse and acceleration/deceleration in T3 Forward/reverse and acceleration/deceleration in T4 Forward/reverse and acceleration/deceleration in T5 Forward/reverse and acceleration/deceleration in T6 Forward/reverse and acceleration/deceleration in T7 |
X 1: Forward run 2: Reverse run Y ... 1 - 4: Acceleration/deceleration time specified |
- - - - - - - |
11 11 11 11 21 21 21 |
|
| 120 | Analog input switching
(for PID, disturb, energy
saving, and set frequency gain)
| 0: No analog input 1: External analog VRF1 (0 - 5 V) 2: External analog VRF1 (0 - 10 V or variable resistor) 3: External analog VRF2 (0 - 5 V) 4: External analog VRF2 (0 - 10 V or variable resistor) 5: External analog IRF (4 - 20 mA) |
1 | 0 | |
| 121 | Disturb modulation rate or simple energy saving rate | 0 - 50% | 1% | 0 | |
| 122 | PID control proportional gain | 0 - 100 | 0.01 | 0.1 | |
| 123 | PID control integral gain | 0 - 100 | 0.01 | 0.1 | |
| 124 | PID control differential gain | 0 - 100 | 0.01 | 0 | |
| 125 | Feedback input filter time constant | 1 - 500 (set value 1 = 10 ms) | 10ms | 10 | |
| 126 | Internal analog output function 1 | 0: No function 1: Set frequency 2: Output frequency 3: Output current 4: DC voltage 5: Fin temperature 6: Load factor (Electrothermal level integrated value) 7: Output of converted analog input value (VRF1 control circuit terminal input) 8: Output of converted analog input value (IRF/VRF2 control circuit terminal input) 9: Output voltage 10: Load factor (Percentage in terms of rated current) 11:Detected speed (option) 12:Output power (V/f mode only) |
1 | 0 | |
| 127 | Internal analog output coefficient 1 | 0 - 20X | by 0.01 | 1 | |
| 128 | Internal analog output function 2 | 0: No function 1: Set frequency 2: Output frequency 3: Output current 4: DC voltage 5: Fin temperature 6: Load factor (Electrothermal level integrated value) 7: Output of converted analog input value (VRF1 control circuit terminal input) 8: Output of converted analog input value (IRF/VRF2 control circuit terminal input) 9: Output voltage 10: Load factor (Percentage in terms of rated current) 11:Detected speed (option) 12:Output power (V/f mode only) |
1 | 0 | |
| 129 | Internal analog output coefficient 2 | 0 - 20X | by 0.01 | 1 | |
| 130 | Direction of rotation of motor
(operation panel) | 1: Forward 2: Reverse |
1 | 1 | |
| 131 | Shortest operation time function | 0 - 99.99 | 0.01 s | 0 | |
| 132 | Reserved | ||||
| 133 | Reserved | ||||
| 134 | Reserved | ||||
| 135 | Reserved | ||||
| 136 | Reserved | ||||
| 137 | Reserved | ||||
| 138 | Reserved | ||||
| 139 | Reserved | ||||
| 140 | Changed code display function | 0 1: Display differences from factory preset 2: Display differences from user’s initialization data |
1 | 0 | |
| 141 | Reserved | ||||
| 142 | Message checksum | 0: No 1: Yes |
1 | 1 | |
| 143 | RS232C/RS485 switching | 1: RS232C 2: RS485 |
1 | 1 | |
| 144 | Pull-up/down function | 0: No 1: Yes |
1 | 0 | |
| 145 | Reserved | ||||
| 146 | Communication function | 0: No function 1: Serial communication function |
1 | 0 | |
| 147 | Inverter No. | 1 - 32 | 1 | 1 | |
| 148 | Communication speed | 1: 1200bps 2: 2400bps 3: 4800bps 4: 9600bps 5: 19200bps |
1 | 3 | |
| 149 | Parity bit | 0: No 1: Odd 2: Even |
1 | 1 | |
| 150 | Stop bit | 1: 1 bit 2: 2 bits |
1 | 1 | |
| 151 | End bit | 0: CR, LF 1: CR |
1 | 0 | |
| 152 | Inverter’s response to specified commands | 0: Sent 1: Not sent (Error response sent) 2: Not sent (Error response not sent) |
1 | 0 | |
| 153 | Reserved | ||||
| 154 | Reserved | ||||
| 155 | Reserved | ||||
| 156 | Reserved | ||||
| 157 | Reserved | ||||
| 158 | Reserved | ||||
| 159 | Reserved | ||||
| 160 | Feed pump control selection (Option) | 0: No feed pump control 1-14: Feed pump mode |
1 | 0 | |
| 161 | Motor setting M1 | 0: M1 not used 1: M1 used (This setting is invalid for mode 1-8.) |
1 | 1 | |
| 162 | Motor settingM2 | 0: M2 not used 1: M2 used | 1 | 0 | |
| 163 | Motor setting M3 | 0: M3 not used 1: M3 used | 1 | 0 | |
| 164 | Motor setting M4 | 0: M4 not used 1: M4 used | 1 | 0 | |
| 165 | Motor setting M5 | 0: M5 not used 1: M5 used (This setting is invalid for mode 9-12.) |
1 | 0 | |
| 166 | Motor setting M6 | 0: M6 not used 1: M6 used (This setting is invalid for mode 9-12.) |
1 | 0 | |
| 167 | Motor setting M7 | 0: M7 not used 1: M7 used (This setting is invalid for mode 5-12.) |
1 | 0 | |
| 168 | Magnetic contactor switching time (Tmc) | 0.10-2.00 s | 0.01 s | 1 | |
| 169 | Maximum limiter duration time (Th) | 0.1-10 min | 0.1 min. | 5 | |
| 170 | Minimum limiter duration time (Tl) | 0.1-10 min | 0.1 min. | 5 | |
| 171 | Auxiliary pump switching ratio (K) | 30-95% | 1% | 50 | |
| 172 | Auxiliary pump return determining time (Tp) | 0.1-10 min | 0.1% | 5 | |
| 173 | Full-voltage starting acceleration time (Ta) | 0.1-25.5 s | 0.1 s | 5 | |
| 174 | Full-voltage starting deceleration time (Td) | 0.1-25.5 s | 0.1 s | 5 | |
| 175 | Pressure command (Pref) | 0-9.999MPa | 0.001 MPa | 0 | |
| 176 | Analog feedback bias pressure (Pb) | 0-± 9.999 MPa | 0.001MPa | P0 | |
| 177 | Analog feedback gain pressure (Pg) | 0-± 9.999 MPa | 0.001MPa | P0 | |
| 178 | Upper pressure value limit (Ph) | 0.001-9.999MPa | 0.001MPa | 1 | |
| 179 | Lower limit pressure value Pl | 0-9.999MPa | 0.001MPa | 0 | |
| 180 | Gradient of pressure acceleration /deceleration |
0.001-9.999MPa | 0.001MPa | 0.1 | |
| 181 | Motor switching allowable deviation | 0-20% | 0.1% | 0 | |
| 182 | 2nd pressure command (Pref2) | 0-9.999MPa | 0.001MPa | 0 | |
| 183 | Maximum limiter duration time (Th2) | 0.1-10 min | 0.1 min. | 5 | |
| 184 | Minimum limiter duration time (Tl2) | 0.1-10 min | 0.1 min. | 5 | |
| 185 | Regular pump switching time (Tch) | 0-720, 999 h | 1 h | 0 | |
| 186 | Regular pump switching signal output time (Tchs) | 0-120 s | 1 s | 120 | |
| 187 | Motor switching function | 0: Select by function code 1: Select by external signal |
1 | 0 | |
| 191 192 193 194 195 196 |
Relay output function (RY3) Relay output function (RY4) Relay output function (RY5) Relay output function (RY6) Relay output function (RY7) Relay output function (RY8) Operation contact ON (optional) |
0:Output at alarm status 1: In operation 2: Low voltage 3: End of simple scheduled operation 4: In operation 2 5: Frequency matching (1st speed frequency) 6: Frequency matching (1st to 8th speed frequencies) 7: Frequency approach 8: Overload alarm level setting (Cd048 value.Output only in constant operation.) 9: Electrothermal level signal (Electrothermal 80%) 10: Fin heat prediction signal 11: Reserved 12: Reserved 13: Excitation and DC braking 14: Lower frequency limit matching 15: Upper frequency limit matching 16: Reserved 17: Reserved 18: FR signal 19: RR signal 20: 2DF signal 21: 3DF signal 22: AD2 signal 23: AD3 signal 24: JOG signal 25: MBS signal 26: ES signal 27: RST signal 28: Reserved 29: Reserved 30: Discharge resistor ON-signal 31 - 33: Reserved 34: Overload alarm signal (Cd048 value. Output when in operation.) 35 - 99: Reserved (*): Option |
1 | 1 5 6 8 10 13 |
|
| 197 | Point to Point control position limiter | 1 - 32767 mm | 1mm | 32767 | |
| 198 | Point to Point control smallest position unit | 1: 1 mm 2: 0.1 mm 3: 0.01 mm |
1 | 1 | |
| 199 | Simple backlash calibration | 0 - ±5000 pulses | 1 pulse | P0 | |
| 600 | Command pulse format | 1: Forward and reverse pulse train 2: Coded pulse train 3: Two-phase pulse train |
1 | 1 | |
| 601 | Command pulse logic | 1: Positive logic 2: Negative logic |
1 | 1 | |
| 602 | PG pulse output divisor | 1: 1/1 2: 1/2 3: 1/4 4: 1/8 5: 1/16 |
1 | 1 | |
| 603 | Deviation counter clear mode | 1: Level operation (the counter is cleared
when it is on.) 2: Edge operation (the counter is cleared when it is on.) |
1 | 2 | |
| 604 | PG pulse multiplication value | 1: × 1 2: × 2 3: × 4 |
1 | 3 | |
| 605 | PG switch | 1: Compatible with line driver PG 2: Compatible with open collector PG |
1 | 1 | |
| 606 | Position control gain | 0.1 - 50 rad/s | 0.1 rad/s | 1 | |
| 607 | Positioning complete width | 0 - 32767 pulses | 1 pulse | 100 | |
| 608 | Error level limit | 0: No alarm function 1 - 1000 (set value 1=1000 pulses) |
1000 pulses | 100 | |
| 609 | Position control acceleration/deceleration | 0: Inactive 1: Active |
1 | 1 | |
| 610 | Number of pulses within 1 mm | 0: Pulse is specified with Cd0611 1 - 32767 pulses |
1 pulse | 0 | |
| 611 | Point to Point control position command | 0: No control 0.01 - 32767 mm |
0.01 - 1 mm | 0 | |
| 612 | Electric gear function selection | 0: Inactive 1: Active |
1 | 0 | |
| 613 | Electric gear A data | 1 - 100 (Setting accuracy: 1) | 1 | 1 | |
| 614 | Electric gear B data | 1 - 100 (Setting accuracy: 1) | 1 | 1 | |
| 615 | Zero servo control function selection | 0: No function 1: Zero servo switching at zero-speed 2: Zero servo switching at external terminal (PO) |
1 | 0 | |
| 616 | Zero-speed | 1 - 3000 rpm | 1rpm | 30 | |
| 617 | Zero servo complete width | 5 - 10000 pulses | 1 pulse | 10 | |
| 618 | Number of PG pulses | 500 - 2048 pulses | 1 pulse | 1000 | |
| 619 | Observer gain setting ration | 0 to 7.8 (This function is invalid for SHF-75K or higher and SPF-90K or higher) | 0.01 | 0 | |
| 620 | Observer time constant | 0 - 7.8 (SHF-75K or higher, function invalid for SPF-90K or higher) | 0.01 | 1 | |
| 630 631 632 633 634 635 636 637 |
Selection of input terminal DI1 Selection of input terminal DI2 Selection of input terminal DI3 Selection of input terminal DI4 Selection of input terminal DI5 Selection of input terminal DI6 |
0: Not used 1: FR 2: RR 3:2DF 4:3DF 5: MBS 6: ES 7: RST 8: AD2 9:AD3 10:JOG 11: FR+JOG 12: RR+JOG 13: FR+AD2 14: RR+AD2 15: FR+AD3 16: RR+AD3 17: FR+2DF 18: RR+2DF 19: FR+3DF 20: RR+3DF 21: FR+2DF+3DF 22: RR+2DF+3DF 23: FR+AD2+2DF 24: RR+AD2+2DF 25: FR+AD2+3DF 26: RR+AD2+3DF 27: FR+AD2+2DF+3DF 28: RR+AD2+2DF+3DF 29: FR+AD3+2DF 30: RR+AD3+2DF 31: FR+AD3+3DF 32: RR+AD3+3DF 33: FR+AD3+2DF+3DF 34: RR+AD3+2DF+3DF 35:PTR 36: IF 37: 5DF 38: HD 39:2P(*) 40:2PT(*) 41:TCL(*) 42:2P+2PT(*) 43:CP 44:CCL 45:PC 46:PID 47:PM1(*) 48:PM2(*) 49:PM3(*) 50:PM4(*) 51:PM5(*) 52:PM6(*) 53:PM7(*) 54: Reserved 55:P0 56:FR+CCL(*) 57:RR+CCL(*) 58-61: Reserved 62:FR+MBS 63:RR+MBS 64: Reserved 65:2DF+AD2 66:2DF+AD3 67:3DF+AD2 68:3DF+AD3 69:A × 10 (*) 70:A × 100 (*) 71-99: Reserved (*):Option |
1 | 1 2 3 4 5 6 7 8 |
|
| 638 639 640 |
Selection of output terminal DO1 Selection of output terminal DO2 Selection of output terminal DO3 |
0: Not used 1: In operation 1 2: Low voltage 3: End of simple scheduled operation 4: In operation 2 5: Frequency matching (1st speed frequency) 6: Frequency matching (1st to 8th speed frequencies) 7: Frequency approach 8: Overload alarm level setting (Cd048 value. Output only in constant operation.) 9: Electrothermal level signal (Electrothermal 80%) 10: Fin heat prediction signal 11: Auxiliary pump driving signal (*) 12: Regular pump switching signal (*) 13: Excitation and DC braking 14: Lower frequency limit matching 15: Upper frequency limit matching 16: Servo on signal (option) 17: Zero servo completion signal (option) 18: FR signal 19: RR signal 20: 2DF signal 21: 3DF signal 22: AD2 signal 23: AD3 signal 24: JOG signal 25: MBS signal 26: ES signal 27: RST signal 28 : Switching standby signal (*) 29: Positioning completion signal (option) 30: Discharge resistor on signal 31: Reserved 32: Frequency counter output (Output frequency) 33: Frequency counter output (Command frequency) 34: Overload alarm signal (Cd048 value. Output when in operation.) 35 - 99: Reserved (*): Option |
1 | 1 5 8 |
|
| 641 | Start standby time | 0 - 120 | 0.1 s | 0 | |
| 642 | Start standby frequency | 0.05 - 60 | 0.01Hz | 5 | |
| 669 | V/f separation command voltage | 0: No function (VRF1 command) 0.01 to 10.23 |
0.01V | 0 | |
| 670 | Magnification of frequency counter output | 1-10 | by 1 | 1 | |
| 671 | Cooling fan ON function
Note: Supported only for cooling fan ON/OFF control model |
0: Cooling fan ON/OFF control 1: Cooling fan ON normally |
1 | 0 | |
| 672 | Missing phase detection function | 0: Missing input phase detection is invalid,missing output phase detection is invalid. 1: Missing input phase detection is valid, missing output phase detection is invalid. 2: Missing input phase detection is invalid, missing output phase detection is valid. 3: Missing input phase detection is valid, missing output phase detection is valid. |
1 | 3 | |
| 673 | Overvoltage stalling prevention function | 0: Overvoltage stalling prevention function inactive. 1: Overvoltage stalling prevention function active. |
1 | 1 | |
| 674 | Relay contact output selection |
0:Output at alarm status 1: In operation 1 2: Low voltage 3: End of simple scheduled operation 4: In operation 2 5: Frequency matching (1st speed frequency) 6: Frequency matching (1st to 8th speed frequencies) 7: Frequency approach 8: Overload alarm level setting (Cd048 value. Output only in constant operation.) 9: Electrothermal level signal (Electrothermal 80%) 10: Fin heat prediction signal 11: Auxiliary pump driving signal (*) 12: Regular pump switching signal (*) 13: Excitation and DC braking 14: Lower frequency limit matching 15: Upper frequency limit matching 16: Servo ON-signal (*) 17: Zero servo completion signal (*) 18: FR signal 19: RR signal 20: 2DF signal 21: 3DF signal 22: AD2 signal 23: AD3 signal 24: JOG signal 25: MBS signal 26: ES signal 27: RST signal 28: Switching standby signal (*) 29: Positioning completion signal (*) 30: Discharge resistor ON-signal 31 - 33: Reserved 34: Overload alarm signal (Cd048 value. Output when in operation.) 35 - 99: Reserved (*): Option |
1 | 0 | |
| 675 | Optional V/f pattern intermediate voltage 1 | 0-460 V | 1V | 0 | |
| 676 | Optional V/f pattern intermediate voltage 2 | 0-460 V | 1V | 0 | |
| 677 | Optional V/f pattern intermediate frequency 1 | 0.05-600 Hz | 0.01Hz | 20 | |
| 678 | Optional V/f pattern intermediate frequency 2 | 0.05-600 Hz | 0.01Hz | 40 | |
| 679 | Current output magnification (option) | 0-20 | ×0.01 | 1 | |
| 680 | Feedback signal disconnection detection time | 0-120 seconds 120: Function invalid | 0.01 s | 5 |
*1 Typical constants for each model are entered.
*2 - *9 See the following table:
| Model | *2 Cd019 |
*3 Cd020 |
*4 Cd021 |
*5 Cd022 |
*6 Cd023 |
*7 Cd024 |
*8 Cd025 |
*9 Cd026 |
|---|---|---|---|---|---|---|---|---|
| SBT-0.75K/1.5K to 7.5K/11K SHF-1.5K to SHF-7.5K SPF-2.2K to SPF-11K |
5 | 10 | 15 | 20 | 5 | 10 | 15 | 20 |
| SBT-11K/15K,1 5K/18.5K SHF-11K, 15K SPF-15K, 18.5K |
15 | 30 | 45 | 60 | 15 | 30 | 45 | 60 |
| SBT-18.5K/22K,2 2K/30K SBT-30K to SBT-55K SHF-18.5K to SHF-55K SPF-22K to SPF-75K |
30 | 60 | 90 | 120 | 30 | 60 | 90 | 120 |
| SHF-75K, 90K SPF-90K, 110K |
60 | 120 | 180 | 240 | 60 | 120 | 180 | 240 |
| SHF-110K to SHF-250K SPF-132K to SPF-315K |
75 | 150 | 225 | 300 | 75 | 150 | 225 | 300 |