SAMCO-vm05 Series (SHF/SPF, SBT)

Function Codes

Code No.
Cd
Function Data Setting resolution Factory Setting User’s
Setting
000 Display selection 1: Frequency (Hz)
2: Output current
3: Speed of rotation (rpm)
4: Load factor
5: Output voltage
6: Pressure value
7: No units display
1 1  
001 Operation command selection 1: Operation panel
2: External terminal signal
3: Communication
1 1  
002 1st speed frequency setting 1: Operation panel
2: External analog VRF1 (0 - 5 V)
3: External analog VRF1 (0 - 10 V or
variable resistor)
4: External analog VRF2 (0 - 5 V)
5: External analog VRF2 (0 - 10 V or
variable resistor)
6: External analog IRF (4 - 20 mA)
7: External analog VRF1 + VRF2
8: External analog VRF1 - VRF2
9: External analog VRF2 - VRF1
10: External analog VRF1 + IRF
11: External analog VRF1 - IRF
12: External analog IRF - VRF1
13: Terminal board step
14: Communication
15: BINARY (option)
16: BCD (option)
1 1  
003 V/f pattern 1: Linear pattern 1 1
2: Square-law decreasing pattern (weak)
3: Square-law decreasing pattern (strong)
1 1  
004 Torque boost 0 - 20% (maximum voltage ratio) 0.1% *1  
005 Base voltage 200 V system
0: No AVR
30 - 240 V
1V *1  
400 V system: 0: No AVR 30 to 460 V
006 Base frequency 0.1 - 60 Hz 0.01Hz *1  
007 Upper frequency limit 30 - 600 Hz 0.01Hz 60  
008 Lower frequency limit 0.05 - 200 Hz 0.01Hz 0.05  
009 Starting method 1: Starting frequency
2: Flying start
3: Starting frequency after DC braking
1 1  
010 Starting frequency 0.05 - 20 Hz 0.01Hz 1  
011 Operation start frequency 0 - 20 Hz 0.01Hz 0  
012 Start delay time 0 - 5 sec. 0.1 s 0  
013 Braking method 1: Deceleration to stop 1 1
2: Deceleration to stop + DC braking
3: Free run stop
1 1  
014 DC braking start frequency 0.2 - 20 Hz 0.01Hz 0.5  
015 DC braking time 0.1 - 10 sec. 0.1 s 2  
016 DC braking force 1 - 10 1 5  
017 Acceleration/deceleration curve 1: Linear
2: S-shaped
1 1  
018 Reference acceleration/ deceleration frequency 10 - 120 Hz 0.01 Hz *1  
019 1st acceleration time 0 - 6500 sec. 0.1 s *2  
020 2nd acceleration time 0 - 6500 sec. 0.1 s *3  
021 3rd acceleration time 0 - 6500 sec. 0.1 s *4  
022 4th acceleration time 0 - 6500 sec. 0.1 s *5  
023 1st deceleration time 0 - 6500 sec. 0.1 s *6  
024 2nd deceleration time 0 - 6500 sec. 0.1 s *7  
025 3rd deceleration time 0 - 6500 sec. 0.1 s *8  
026 4th deceleration time 0 - 6500 sec. 0.1 s *9  
027 JOG acceleration/deceleration time 0.1 - 60 Hz 0.1 s 0.1  
028 Jog frequency 0.1 - 60 Hz 0.01Hz 5  
029 1st speed frequency 0 to 600 Hz 0.01Hz 0  
030 2nd speed frequency 0 to 600 Hz 0.01Hz 10  
031 3rd speed frequency 0 to 600 Hz 0.01Hz 20  
032 4th speed frequency 0 to 600 Hz 0.01Hz 30  
033 5th speed frequency 0 to 600 Hz 0.01Hz 40  
034 6th speed frequency 0 to 600 Hz 0.01Hz 50  
035 7th speed frequency 0 to 600 Hz 0.01Hz 60  
036 8th speed frequency 0 to 600 Hz 0.01Hz 0  
037 1st Jump frequency lower limit 0 to 600 Hz 0.01Hz 0  
038 1st jump top frequency 0 to 600 Hz 0.01Hz 0  
039 2nd jump bottom frequency 0 to 600 Hz 0.01Hz 0  
040 2nd jump top frequency 0 to 600 Hz 0.01Hz 0  
041 3rd jump bottom frequency 0 to 600 Hz 0.01Hz 0  
042 3rd jump top frequency 0 to 600 Hz 0.01Hz 0  
043 Output current limiting H characteristic/SHF 0: No function 50 - 200% 1% 150  
P characteristic/SPF 0: No function 50 - 150% 1% 120  
044 Electrothermal level setting 0: No function 20 - 105% 1% 100  
045 Output current limiting during constant power operation 0: No
1: Yes V/F mode only
(Currently selected acceleration/deceleration time)
2: Yes V/F mode only
(Acceleration/Deceleration time = Cd019,
Cd023: 1st acceleration/deceleration time)
3: Yes V/F mode only
(Acceleration/Deceleration time = Cd020,
Cd024: 2nd acceleration/deceleration time)
4: Yes V/F mode only
(Acceleration/Deceleration time = Cd021,
Cd025: 3rd acceleration/deceleration time)
5: Yes V/F mode only
(Acceleration/Deceleration time = Cd022,
Cd026: 4th acceleration/deceleration time)
6: Yes V/F mode and sensorless vector control
mode (Acceleration/Deceleration time = Cd019,
Cd023: 1st acceleration/deceleration time)
7: Yes V/F mode and sensorless vector control
mode (Acceleration/Deceleration time = Cd020,
Cd024: 2nd acceleration/deceleration time)
8: Yes V/F mode and sensorless vector control
mode (Acceleration/Deceleration time = Cd021,
Cd025: 3rd acceleration/deceleration time)
9: Yes V/F mode and sensorless vector control
mode (Acceleration/Deceleration time = Cd022,
Cd026: 4th acceleration/deceleration time)
1 0  
046 Restart after momentary power failure 0: Do not restart.
1: Restart.
2: Compensation for momentary power failure
1 0  
047 Auto alarm recovery 0: No auto alarm recovery function
1: Auto alarm recovery function
1 0  
048 Overload alarm level setting H characteristic/SHF 20 - 200% 1% 150  
P characteristic/SPF 20 - 150% 1% 120  
049 Duty cycle of brake resistor 0: No brake resistor
2 - 25% ED
99: External brake unit
1%ED *1  
050 Direction of rotation of motor

Note: Cd130 for direction command
from the operation panel

1: Forward and reverse run
2: Forward run only
3: Reverse run only
1 1  
051 Carrier frequency 0 - 130 1 *1  
052 Motor type 1: General-purpose motor
2: Inverter dedicated motor
1 1  
053 Motor poles, voltage, and capacity XYZZZ
X: Number of motor poles
Y: Rated voltage
Z: Motor capacity
- *1  
054 Bias frequency (VRF1) 0 to ±600 Hz (frequency at 0 V) 0.1Hz P0  
055 Gain frequency (VRF1) 0 to ±600 Hz (frequency at 5 V or 10 V) 0.1Hz P60  
056 Approach frequency 0 - 600 Hz 0.01Hz 10  
057 Frequency matching range 0 - 10 Hz 0.01Hz 0  
058 No-unit display amplification 0 to 100
(amplification in relation to output frequency)
× 0.01 1  
059 Display selection 1: No units (multiple of CD058)
2: PID feedback frequency [Hz]
3: Command pressure [MPa] (option)
4: Set pressure [MPa] (option)
5: Command frequency [Hz]
6: Fin temperature [°C]
7: Detecting speed [rpm] (option)
8: Regular pump switching integrated time
[H] (option)
9 - 10: Reserved
11: Detecting position [mm] (option)
12: DC voltage [V]
13: Output power [kW] (V/f mode only)
1 1  
060 Rating selection

Note: This function is for SBT series only.

1: H characteristic (150% rating)
2: P characteristic (120% rating)
1 1  
061 Instability elimination 0 - 20 1 *1  
062 Bias frequency (IRF/VRF2) 0 to ± 600 Hz (frequency at 5 V or 10 V or 20 mA) 0.1Hz P0  
063 Gain frequency (IRF/VRF2) 0 to ±600 Hz (frequency at 5 V or 10 V or 20 mA) 0.1Hz P60  
064 Discharge resistor on signal output time 0.01 - 10 s 0.01 s 0.1  
065 Set frequency gain 0 - 100% 1 0  
066 V·f separate function selection 1: V·f comparison
2: Complete separation
1 1  
067 MBS terminal input mode 1: Level operation
2: Edge operation
1 1  
068 Internal analog output bias 1 0 - ±10.0 V 0.1V P0  
069 Internal analog output bias 2 0 - ±10.0 V 0.1V P0  
070 ES input terminal function 1: NO external thermal signal
2: NC external thermal signal
1 1  
071 Motor control mode selection 1: V/f control mode
2: Sensorless vector control mode
3: Internal PID control mode
4: Position control (optional)
5: Speed control (optional)
6: Simple energy-saving mode
7: Auto energy-saving mode 1
8: Auto energy-saving mode 2
9: Auto tuning mode 1
10: Auto tuning mode 2
11: V·f separate control
12: Switching between sensorless vector
control and V/f control
1 1  
072 Torque limiter (power running) H characteristic/SHF: 5 - 200% 1% 100  
P characteristic/SPF: 5 - 150%
073 Torque limiter (regeneration) 5 - 100% 1% *1  
074 Multiple for starting excitation current 1 - 10 (for applicable motor) 1 5  
075 Striking excitation time 0 - 10 (for no starting excitation) 0.1 s *1  
076 Multiple for braking excitation current 1 - 10 (for applicable motor) 1 5  
077 Braking excitation time 0 - 10 (for no starting excitation) 0.1 s 1  
078 Motor current rating Approx. 30 - 110% of inverter current rating 0.1A *1  
079 Motor frequency rating 1: 50 Hz
2: 60 Hz
1 *1  
080 Motor speed rating 0 to 24000 rpm 1rpm *1  
081 Motor isolation type 1: Type A
2: Type E
3: Type B
4: Type F
5: Type H
1 *1  
082 Speed adjustment gain 0.5 to 2 0.01 1  
083 External analog input filter time constant 1 - 500 (set value: 1 = 10 ms) 10ms 10  
084 Copy function 1: Transfer the current code data to the operation panel
2: Transfer the operation panel memory to
the inverter
1 0  
085 Torque limiter analog input function (power running) 0: Limit using Cd072
1: Limit using the signal on the VRF1
terminal (0 to 5 V)
2: Limit using the signal on the VRF1
terminal (0 to 10 V or variable resistor)
3: Limit using the signal on the VRF2
terminal (0 to 5 V)
4: Limit using the signal on the VRF2
terminal (0 to 10 V or variable resistor)
5: Limit using the signal on the IRF terminal
(4 to 20 mA)
1 0  
086 Torque limiter analog input function (regeneration) 0: Limit using Cd073
1: Limit using the signal on the VRF1
terminal (0 to 5 V)
2: Limit using the signal on the VRF1
terminal (0 to 10 V or variable resistor)
3: Limit using the signal on the VRF2
terminal (0 to 5 V)
4: Limit using the signal on the VRF2
terminal (0 to 10 V or variable resistor)
5: Limit using the signal on the IRF
terminal (4 to 20 mA)
1 0  
087 Function to switch between “OV” and “LV” alarms when stopped 0: OV enabled, LV disabled during stop
1: OV disabled, LV enabled during stop
2: OV disabled, LV disabled during stop
3: OV enabled, LV enabled during stop
1 0  
088 ASR proportional gain 0 - 7.8 0.01 *1  
089 ASR integral gain 0 - 106 0.01 *1  
090 Start of S-shaped acceleration 0 - 100% 1% 50  
091 End of S-shaped acceleration 0 - 100% 1% 50  
092 Gradient of middle of S-shaped acceleration 0 - 100% 1% 0  
093 Start of S-shaped deceleration 0 - 100% 1% 50  
094 End of S-shaped deceleration 0 - 100% 1% 50  
095 Gradient of middle of S-shaped deceleration 0 - 100% 1% 0  
096 Function lock 0: Code data changeable (No lock function)
1:Code data unchangeable (except Cd096)
2:Code data unchangeable (except Cd096
and Cd028 to Cd036)
3: Code data unchangeable (except Cd096 or
using communication function)
4: Code data unchangeable (except for Cd096,
Cd175 or Cd182, pressure command.)
1 0  
097 Operation time display Read only 1 hour ---  
098 Reading alarm data 0
1: Read start
9: Record erase
1 0  
099 Data initialization 0
1: Initialize factory presets
2: Invalid constant by auto tuning
3: Initialize user’s data
99:Set user’s initialization value
1 0  
100 Operation panel remote/local
selection
0
1: Toggle function (optional)
1 0  
101 Operation mode selection 0: Normal operation
1: Simple scheduled operation
2: Disturbed operation
1 0  
102 Simple scheduled operation
repetition
0: Continuous
1 - 250: Repetition count
1 1  
103 Operation timer T1 0 - 6500 s 1 s 10  
104 Operation timer T2 0 - 6500 s 1 s 10  
105 Operation timer T3 0 - 6500 s 1 s 10  
106 Operation timer T4 0 - 6500 s 1 s 10  
107 Operation timer T5 0 - 6500 s 1 s 10  
108 Operation timer T6 0 - 6500 s 1 s 10  
109 Operation timer T7 0 - 6500 s 1 s 10  
110 Operation stop timer T0 0 - 6500 s 1 s 10  
111 Midway stop deceleration time 1 - 4: Data of Cd023 - Cd026 1 1  
112 Midway start acceleration time 1 - 4: Data of Cd019 - Cd022 1 1  
113
114
115
116
117
118
119
Forward/reverse and acceleration/deceleration in T1
Forward/reverse and acceleration/deceleration in T2
Forward/reverse and acceleration/deceleration in T3
Forward/reverse and acceleration/deceleration in T4
Forward/reverse and acceleration/deceleration in T5
Forward/reverse and acceleration/deceleration in T6
Forward/reverse and acceleration/deceleration in T7
X 1: Forward run
2: Reverse run
Y ... 1 - 4: Acceleration/deceleration time specified
-
-
-
-
-
-
-
11
11
11
11
21
21
21
 
120 Analog input switching (for PID, disturb, energy saving, and set frequency gain)

 

0: No analog input
1: External analog VRF1 (0 - 5 V)
2: External analog VRF1 (0 - 10 V or
variable resistor)
3: External analog VRF2 (0 - 5 V)
4: External analog VRF2 (0 - 10 V or
variable resistor)
5: External analog IRF (4 - 20 mA)
1 0  
121 Disturb modulation rate or simple energy saving rate 0 - 50% 1% 0  
122 PID control proportional gain 0 - 100 0.01 0.1  
123 PID control integral gain 0 - 100 0.01 0.1  
124 PID control differential gain 0 - 100 0.01 0  
125 Feedback input filter time constant 1 - 500 (set value 1 = 10 ms) 10ms 10  
126 Internal analog output function 1 0: No function
1: Set frequency
2: Output frequency
3: Output current
4: DC voltage
5: Fin temperature
6: Load factor (Electrothermal level integrated
value)
7: Output of converted analog input value
(VRF1 control circuit terminal input)
8: Output of converted analog input value
(IRF/VRF2 control circuit terminal input)
9: Output voltage
10: Load factor (Percentage in terms of rated
current)
11:Detected speed (option)
12:Output power (V/f mode only)
1 0  
127 Internal analog output coefficient 1 0 - 20X by 0.01 1  
128 Internal analog output function 2 0: No function
1: Set frequency
2: Output frequency
3: Output current
4: DC voltage
5: Fin temperature
6: Load factor (Electrothermal level integrated
value)
7: Output of converted analog input value
(VRF1 control circuit terminal input)
8: Output of converted analog input value
(IRF/VRF2 control circuit terminal input)
9: Output voltage
10: Load factor (Percentage in terms of rated
current)
11:Detected speed (option)
12:Output power (V/f mode only)
1 0  
129 Internal analog output coefficient 2 0 - 20X by 0.01 1  
130 Direction of rotation of motor

(operation panel)

1: Forward
2: Reverse
1 1  
131 Shortest operation time function 0 - 99.99 0.01 s 0  
132 Reserved        
133 Reserved        
134 Reserved        
135 Reserved        
136 Reserved        
137 Reserved        
138 Reserved        
139 Reserved        
140 Changed code display function 0
1: Display differences from factory preset
2: Display differences from user’s
initialization data
1 0  
141 Reserved        
142 Message checksum 0: No
1: Yes
1 1  
143 RS232C/RS485 switching 1: RS232C
2: RS485
1 1  
144 Pull-up/down function 0: No
1: Yes
1 0  
145 Reserved        
146 Communication function 0: No function
1: Serial communication function
1 0  
147 Inverter No. 1 - 32 1 1  
148 Communication speed 1: 1200bps
2: 2400bps
3: 4800bps
4: 9600bps
5: 19200bps
1 3  
149 Parity bit 0: No
1: Odd
2: Even
1 1  
150 Stop bit 1: 1 bit
2: 2 bits
1 1  
151 End bit 0: CR, LF
1: CR
1 0  
152 Inverter’s response to specified commands 0: Sent
1: Not sent (Error response sent)
2: Not sent (Error response not sent)
1 0  
153 Reserved        
154 Reserved        
155 Reserved        
156 Reserved        
157 Reserved        
158 Reserved        
159 Reserved        
160 Feed pump control selection (Option) 0: No feed pump control
1-14: Feed pump mode
1 0  
161 Motor setting M1 0: M1 not used 1: M1 used
(This setting is invalid for mode 1-8.)
1 1  
162 Motor settingM2 0: M2 not used 1: M2 used 1 0  
163 Motor setting M3 0: M3 not used 1: M3 used 1 0  
164 Motor setting M4 0: M4 not used 1: M4 used 1 0  
165 Motor setting M5 0: M5 not used 1: M5 used
(This setting is invalid for mode 9-12.)
1 0  
166 Motor setting M6 0: M6 not used 1: M6 used
(This setting is invalid for mode 9-12.)
1 0  
167 Motor setting M7 0: M7 not used 1: M7 used
(This setting is invalid for mode 5-12.)
1 0  
168 Magnetic contactor switching time (Tmc) 0.10-2.00 s 0.01 s 1  
169 Maximum limiter duration time (Th) 0.1-10 min 0.1 min. 5  
170 Minimum limiter duration time (Tl) 0.1-10 min 0.1 min. 5  
171 Auxiliary pump switching ratio (K) 30-95% 1% 50  
172 Auxiliary pump return determining time (Tp) 0.1-10 min 0.1% 5  
173 Full-voltage starting acceleration time (Ta) 0.1-25.5 s 0.1 s 5  
174 Full-voltage starting deceleration time (Td) 0.1-25.5 s 0.1 s 5  
175 Pressure command (Pref) 0-9.999MPa 0.001 MPa 0  
176 Analog feedback bias pressure (Pb) 0-± 9.999 MPa 0.001MPa P0  
177 Analog feedback gain pressure (Pg) 0-± 9.999 MPa 0.001MPa P0  
178 Upper pressure value limit (Ph) 0.001-9.999MPa 0.001MPa 1  
179 Lower limit pressure value Pl 0-9.999MPa 0.001MPa 0  
180 Gradient of pressure acceleration
/deceleration
0.001-9.999MPa 0.001MPa 0.1  
181 Motor switching allowable deviation 0-20% 0.1% 0  
182 2nd pressure command (Pref2) 0-9.999MPa 0.001MPa 0  
183 Maximum limiter duration time (Th2) 0.1-10 min 0.1 min. 5  
184 Minimum limiter duration time (Tl2) 0.1-10 min 0.1 min. 5  
185 Regular pump switching time (Tch) 0-720, 999 h 1 h 0  
186 Regular pump switching signal output time (Tchs) 0-120 s 1 s 120  
187 Motor switching function 0: Select by function code
1: Select by external signal
1 0  
191
192
193
194
195
196
Relay output function (RY3)
Relay output function (RY4)
Relay output function (RY5)
Relay output function (RY6)
Relay output function (RY7)
Relay output function (RY8)
Operation contact ON (optional)

0:Output at alarm status
1: In operation
2: Low voltage
3: End of simple scheduled operation
4: In operation 2
5: Frequency matching (1st speed frequency)
6: Frequency matching (1st to 8th speed frequencies)
7: Frequency approach
8: Overload alarm level setting (Cd048 value.Output only in constant operation.)
9: Electrothermal level signal (Electrothermal 80%)
10: Fin heat prediction signal
11: Reserved
12: Reserved
13: Excitation and DC braking
14: Lower frequency limit matching
15: Upper frequency limit matching
16: Reserved
17: Reserved
18: FR signal 19: RR signal
20: 2DF signal 21: 3DF signal
22: AD2 signal 23: AD3 signal
24: JOG signal 25: MBS signal
26: ES signal 27: RST signal
28: Reserved
29: Reserved
30: Discharge resistor ON-signal
31 - 33: Reserved
34: Overload alarm signal (Cd048 value.
Output when in operation.)
35 - 99: Reserved (*): Option
1 1
5
6
8
10
13
 
197 Point to Point control position limiter 1 - 32767 mm 1mm 32767  
198 Point to Point control smallest position unit 1: 1 mm
2: 0.1 mm
3: 0.01 mm
1 1  
199 Simple backlash calibration 0 - ±5000 pulses 1 pulse P0  
600 Command pulse format 1: Forward and reverse pulse train
2: Coded pulse train
3: Two-phase pulse train
1 1  
601 Command pulse logic 1: Positive logic
2: Negative logic
1 1  
602 PG pulse output divisor 1: 1/1
2: 1/2
3: 1/4
4: 1/8
5: 1/16
1 1  
603 Deviation counter clear mode 1: Level operation (the counter is cleared when it is on.)
2: Edge operation (the counter is cleared
when it is on.)
1 2  
604 PG pulse multiplication value 1: × 1
2: × 2
3: × 4
1 3  
605 PG switch 1: Compatible with line driver PG
2: Compatible with open collector PG
1 1  
606 Position control gain 0.1 - 50 rad/s 0.1 rad/s 1  
607 Positioning complete width 0 - 32767 pulses 1 pulse 100  
608 Error level limit 0: No alarm function
1 - 1000 (set value 1=1000 pulses)
1000 pulses 100  
609 Position control acceleration/deceleration 0: Inactive
1: Active
1 1  
610 Number of pulses within 1 mm 0: Pulse is specified with Cd0611
1 - 32767 pulses
1 pulse 0  
611 Point to Point control position command 0: No control
0.01 - 32767 mm
0.01 - 1 mm 0  
612 Electric gear function selection 0: Inactive
1: Active
1 0  
613 Electric gear A data 1 - 100 (Setting accuracy: 1) 1 1  
614 Electric gear B data 1 - 100 (Setting accuracy: 1) 1 1  
615 Zero servo control function selection 0: No function
1: Zero servo switching at zero-speed
2: Zero servo switching at external terminal (PO)
1 0  
616 Zero-speed 1 - 3000 rpm 1rpm 30  
617 Zero servo complete width 5 - 10000 pulses 1 pulse 10  
618 Number of PG pulses 500 - 2048 pulses 1 pulse 1000  
619 Observer gain setting ration 0 to 7.8 (This function is invalid for SHF-75K or higher and SPF-90K or higher) 0.01 0  
620 Observer time constant 0 - 7.8 (SHF-75K or higher, function invalid for SPF-90K or higher) 0.01 1  
630
631
632
633
634
635
636
637
Selection of input terminal DI1
Selection of input terminal DI2
Selection of input terminal DI3
Selection of input terminal DI4
Selection of input terminal DI5
Selection of input terminal DI6
0: Not used 1: FR 2: RR 3:2DF 4:3DF 5: MBS 6: ES 7: RST 8: AD2 9:AD3 10:JOG 11: FR+JOG 12: RR+JOG 13: FR+AD2 14: RR+AD2 15: FR+AD3 16: RR+AD3 17: FR+2DF 18: RR+2DF 19: FR+3DF 20: RR+3DF 21: FR+2DF+3DF
22: RR+2DF+3DF
23: FR+AD2+2DF
24: RR+AD2+2DF
25: FR+AD2+3DF
26: RR+AD2+3DF
27: FR+AD2+2DF+3DF
28: RR+AD2+2DF+3DF 29: FR+AD3+2DF
30: RR+AD3+2DF 31: FR+AD3+3DF
32: RR+AD3+3DF 33: FR+AD3+2DF+3DF
34: RR+AD3+2DF+3DF 35:PTR 36: IF
37: 5DF 38: HD 39:2P(*) 40:2PT(*) 41:TCL(*)
42:2P+2PT(*) 43:CP 44:CCL 45:PC 46:PID
47:PM1(*) 48:PM2(*) 49:PM3(*) 50:PM4(*)
51:PM5(*) 52:PM6(*) 53:PM7(*)
54: Reserved 55:P0
56:FR+CCL(*) 57:RR+CCL(*)
58-61: Reserved
62:FR+MBS 63:RR+MBS 64: Reserved
65:2DF+AD2 66:2DF+AD3 67:3DF+AD2
68:3DF+AD3
69:A × 10 (*) 70:A × 100 (*)
71-99: Reserved (*):Option
1 1
2
3
4
5
6
7
8
 
638
639
640
Selection of output terminal DO1
Selection of output terminal DO2
Selection of output terminal DO3
0: Not used 1: In operation 1
2: Low voltage
3: End of simple scheduled operation
4: In operation 2
5: Frequency matching (1st speed frequency)
6: Frequency matching (1st to 8th speed
frequencies)
7: Frequency approach
8: Overload alarm level setting (Cd048 value.
Output only in constant operation.)
9: Electrothermal level signal
(Electrothermal 80%)
10: Fin heat prediction signal
11: Auxiliary pump driving signal (*)
12: Regular pump switching signal (*)
13: Excitation and DC braking
14: Lower frequency limit matching
15: Upper frequency limit matching
16: Servo on signal (option)
17: Zero servo completion signal (option)
18: FR signal 19: RR signal 20: 2DF signal
21: 3DF signal 22: AD2 signal
23: AD3 signal 24: JOG signal
25: MBS signal 26: ES signal 27: RST signal
28 : Switching standby signal (*)
29: Positioning completion signal (option)
30: Discharge resistor on signal
31: Reserved
32: Frequency counter output (Output frequency)
33: Frequency counter output (Command
frequency)
34: Overload alarm signal (Cd048 value.
Output when in operation.)
35 - 99: Reserved (*): Option
1 1
5
8
 
641 Start standby time 0 - 120 0.1 s 0  
642 Start standby frequency 0.05 - 60 0.01Hz 5  
669 V/f separation command voltage 0: No function (VRF1 command)
0.01 to 10.23
0.01V 0  
670 Magnification of frequency counter output 1-10 by 1 1  
671 Cooling fan ON function

Note: Supported only for cooling fan ON/OFF control model

0: Cooling fan ON/OFF control
1: Cooling fan ON normally
1 0  
672 Missing phase detection function 0: Missing input phase detection is invalid,missing output phase detection is invalid.
1: Missing input phase detection is valid,
missing output phase detection is invalid.
2: Missing input phase detection is invalid,
missing output phase detection is valid.
3: Missing input phase detection is valid,
missing output phase detection is valid.
1 3  
673 Overvoltage stalling prevention function 0: Overvoltage stalling prevention function inactive.
1: Overvoltage stalling prevention function active.
1 1  
674 Relay contact output selection 0:Output at alarm status
1: In operation 1 2: Low voltage
3: End of simple scheduled operation
4: In operation 2
5: Frequency matching (1st speed frequency)
6: Frequency matching (1st to 8th speed
frequencies)
7: Frequency approach
8: Overload alarm level setting (Cd048 value.
Output only in constant operation.)
9: Electrothermal level signal (Electrothermal 80%)
10: Fin heat prediction signal
11: Auxiliary pump driving signal (*)
12: Regular pump switching signal (*)
13: Excitation and DC braking
14: Lower frequency limit matching
15: Upper frequency limit matching
16: Servo ON-signal (*)
17: Zero servo completion signal (*)
18: FR signal 19: RR signal 20: 2DF signal
21: 3DF signal 22: AD2 signal
23: AD3 signal 24: JOG signal
25: MBS signal 26: ES signal 27: RST signal
28: Switching standby signal (*)
29: Positioning completion signal (*)
30: Discharge resistor ON-signal
31 - 33: Reserved
34: Overload alarm signal
(Cd048 value. Output when in operation.)
35 - 99: Reserved (*): Option
1 0  
675 Optional V/f pattern intermediate voltage 1 0-460 V 1V 0  
676 Optional V/f pattern intermediate voltage 2 0-460 V 1V 0  
677 Optional V/f pattern intermediate frequency 1 0.05-600 Hz 0.01Hz 20  
678 Optional V/f pattern intermediate frequency 2 0.05-600 Hz 0.01Hz 40  
679 Current output magnification (option) 0-20 ×0.01 1  
680 Feedback signal disconnection detection time 0-120 seconds 120: Function invalid 0.01 s 5  

: The setting cannot be changed during operation.
*1 Typical constants for each model are entered.
*2 - *9 See the following table:
Model *2
Cd019
*3
Cd020
*4
Cd021
*5
Cd022
*6
Cd023
*7
Cd024
*8
Cd025
*9
Cd026
SBT-0.75K/1.5K to 7.5K/11K
SHF-1.5K to SHF-7.5K
SPF-2.2K to SPF-11K
5 10 15 20 5 10 15 20
SBT-11K/15K,1 5K/18.5K
SHF-11K, 15K
SPF-15K, 18.5K
15 30 45 60 15 30 45 60
SBT-18.5K/22K,2 2K/30K
SBT-30K to SBT-55K
SHF-18.5K to SHF-55K
SPF-22K to SPF-75K
30 60 90 120 30 60 90 120
SHF-75K, 90K
SPF-90K, 110K
60 120 180 240 60 120 180 240
SHF-110K to SHF-250K
SPF-132K to SPF-315K
75 150 225 300 75 150 225 300