SAMCO-e Series
Function Codes
| Code No. Cd |
Function | Data | Setting resolution | Factory preset | User’s setting |
|---|---|---|---|---|---|
| 000 | Display selection | 1: Frequency (Hz) 2: Output current (A) 7: No-unit display |
1 | 1 | |
| 001 | Operation command selection | 1: Operation panel 2: External terminal signal 3: Communication |
1 | 1 | |
| 002 | 1st speed frequency setting | 0: Operation Panel Resistor 1:Operation panell 2: External analog VRF (0 to 5 V) 3: External analog VRF (0 to 10 V or variable resistor) 6: External analog IRF (4 to 20 mA) 10: External analog VRF + IRF 11: External analog VRF - IRF 12: Reserved 13: Reserved 14: Communication |
1 | 0 | |
| 003 | V/f pattern | 1: Linear pattern 2: Square-law decreasing pattern |
1 | 1 | |
| 004 | Torque boost | 0 to 20% (maximum voltage ratio) | 0.1% | *1 | |
| 005 | Base voltage | 200 V system 0: No AVR 30 to 240 V |
1V | *1 | |
| 400 V system 0: No AVR 30 to 460 V |
|||||
| 006 | Base frequency | 0.1 to 400 Hz | 0.1Hz | *1 | |
| 007 | Upper frequency limit | 30 to 400 Hz | 0.1Hz | 60 | |
| 008 | Lower limit frequency | 0.1 to 200 Hz 0.1 Hz | 0.1Hz | 0.1 | |
| 009 | Starting method | 1: Starting frequency 3: Starting frequency after DC braking |
1 | 1 | |
| 010 | Starting frequency | 0.1 to 20 Hz | 0.1Hz | 1 | |
| 011 | Operation start frequency | 0 to 20 Hz | 0.1Hz | 0 | |
| 012 | Start delay time | 0 to 5 sec | 0.1 s | 0 | |
| 013 | Braking method | 1: Deceleration to stop 2: Deceleration to stop + DC braking 3: Free run stop |
1 | 1 | |
| 014 | DC braking start frequency | 0.2 to 20 Hz | 0.1Hz | 0.5 | |
| 015 | DC braking time | 0.1 to 10 sec. | 0.1 s | 2 | |
| 016 | DC braking force | 1 to 10 | 1 | 5 | |
| 018 | Reference acceleration/ deceleration frequency |
10 to 120 Hz | 0.1Hz | *1 | |
| 019 | 1st acceleration time | 0 to 999.9 sec. | 0.1 s | *2 | |
| 020 | 2nd acceleration tim | 0 to 999.9 s | 0.1 s | *3 | |
| 023 | 1st deceleration time | 0 to 999.9 s | 0.1 s | *4 | |
| 024 | 2nd deceleration time | 0 to 999.9 sec. | 0.1 s | *5 | |
| 027 | Jog acceleration/ deceleration time |
0 to 20 s | 0.1 s | 0.1 | |
| 028 | Jog frequency | 0.1 to 60Hz | 0.1Hz | 5 | |
| 029 | 1st speed frequency | 0 to 400Hz | 0.1Hz | 0 | |
| 030 | 2nd speed frequenc | 0 to 400Hz | 0.1Hz | 10 | |
| 031 | 3rd speed frequency | 0 to 400Hz | 0.1Hz | 20 | |
| 032 | 4th speed frequency | 0 to 400Hz | 0.1Hz | 30 | |
| 033 | 5th speed frequency | 0 to 400Hz | 0.1Hz | 40 | |
| 034 | 6th speed frequency | 0 to 400Hz | 0.1Hz | 50 | |
| 035 | 7th speed frequency | 0 to 400Hz | 0.1Hz | 60 | |
| 036 | 8th speed frequency | 0 to 400Hz | 0.1Hz | 0 | |
| 037 | Jump bottom frequency | 0 to 400Hz | 0.1Hz | 0 | |
| 038 | Jump top frequency | 0 to 400Hz | 0.1Hz | 0 | |
| 043 | Output current limiting | 0: No function 50 to 200% |
1% | 150 | |
| 044 | Electrothermal level setting | 0: No function 20 to 105% |
1% | 100 | |
| 045 | Output current limiting during constant power operation |
0: No 1: Yes (Currently selected acceleration/deceleration time) 2: Yes (Acceleration/Deceleration time = Cd019, Cd023: 1st acceleration/deceleration time) 3: Yes (Acceleration/Deceleration time = Cd020, Cd024: 2nd acceleration/deceleration time) |
1 | 0 | |
| 047 | Auto alarm recovery | 0: No auto alarm recovery function 1: Auto alarm recovery function |
1 | 0 | |
| 049 | Duty cycle of brake resistor | 0: No brake resistor 2 to 25% ED |
1%ED | * | |
| 050 |
Direction of rotation of motor Note: Cd130 for direction from the operation panel command |
1: Forward and reverse run 2: Forward run only 3: Reverse run only |
1 | 1 | |
| 051 | Carrier frequency | 0 to 130 | 1 | *1 | |
| 052 | Motor type | 1: General-purpose motor 2: Motor designed specifically for inverter |
1 | 1 | |
| 054 | Bias frequency (VRF) | -99.9 to 400 Hz (frequency at 0 V) | 0.1Hz | 0 | |
| 055 | Gain frequency (VRF) | -99.9 to 400 Hz (frequency at 5 or 10 V) | 0.1Hz | 60 | |
| 056 | Approach frequency | 0 to 400 Hz | 0.1Hz | 10 | |
| 057 | Frequency matching range | 0 to 10 Hz | 0.1Hz | 0 | |
| 058 | Multiple for no-units display | 0 to 99.99 (multiple of the output frequency) | 0.01 | 1 | |
| 059 | Display selection | 1: No units (multiple of CD058) 2: PID feedback frequency [Hz] 3: Load factor [%] 4: Output voltage [V] 5: Reserved 6: Fin temperature [°C] 7-13: Reserved |
1 | 1 | |
| 062 | Bias frequency (IRF) | -99.9 to 400 Hz (frequency at 4 mA) |
0.1 Hz | 0 | |
| 063 | Gain frequency (IRF) | -99.9 to 400 Hz (frequency at 20 mA) |
0.1Hz | 60 | |
| 066 | V•f separate function selection | 1: V/f comparison 2: Complete separation |
1 | 1 | |
| 070 | ES input terminal function | 1: NO external thermal signal 2: NC external thermal signal |
1 | 1 | |
| 071 | Motor control mode selection | 1: V/F control mode 3: Internal PID control mode 7: Auto energy-saving mode 11: V•f separate control |
1 | 1 | |
| 072 to 082 | Reserved | ||||
| 083 | External analog input
Filter time constant |
1 to 500 (set value: 1 = 10 ms) | 10ms | 10 | |
| 084 | Copy function (Option) |
1: Transfer the current code data to the operation panel 2: Transfer the operation panel memory to the inverter |
1 | 0 | |
| 096 | Function lock | 0: Code data changeable (No lock function) 2: Code data unchangeable (except Cd096 and Cd028 to Cd036) |
1 | 0 | |
| 098 | Reading alarm data | 0 1: Read start 9: Record erase |
1 | 0 | |
| 099 | Data initialization | 0 1: Factory setting data initialization |
1 | 0 | |
| 120 | Analog input switchin (for both of the PID and the energy saving functions) |
0: No analog input 1: External analog VRF (0 to 5 V) 2: External analog VRF (0 to 10 V or variable resistor) 5: External analog IRF (4 to 20 mA) |
1 | 0 | |
| 122 | PID control proportional gain | 0 to 99.99 | 0.01 | 0.1 | |
| 123 | PID control integral gain | 0 to 99.99 | 0.01 | 0.1 | |
| 124 | PID control differential gain | 0 to 99.99 | 0.01 | 0 | |
| 125 | Feedback input filter time | 1 to 500 (set value 1 = 10 ms) | 10ms | 10 | |
| 126 | Internal analog output function | 0: No function 1: Set frequency 2: Output frequency 3: Output current 4: Reserved 5: Fin temperature 6: Load factor (Electrothermal level integrated value) 7: Output of converted analog input value (VRF control circuit terminal input) 8: Output of converted analog input value (IRF control circuit terminal input) 9: Output voltage 10: Load factor (Percentage in terms of rated current) 12:Reserved |
1 | 0 | |
| 127 | Internal analog output coefficient | 0 to 20X | by 0.01 | 1 | |
| 130 | Direction of rotation of
motor (Operation panel)
|
1: Forward 2: Reverse |
1 | 1 | |
| 136 | The Bias Frequency (for theFrequency Control on the operation panel).
|
-99.9 to 400 Hz | 0.1Hz | 0 | |
| 137 | The Gain Frequency (for the Frequency Control on the operation panel).
|
-99.9 to 400 Hz | 0.1Hz | 60 | |
| 140 | Changed code display function | 0 1: Display differences from factory preset |
1 | 0 | |
| 142 | Message checksum | 0: No 1: Yes |
1 | 1 | |
| 144 | Pull-up/down function | 0: No 1: Yes |
1 | 0 | |
| 146 | Communication function | 0: No function 1: Serial communication function |
1 | 0 | |
| 147 | Inverter No. | 1 to 32 | 1 | 1 | |
| 148 | Communication speed | 1: 1200bps 2: 2400bps 3: 4800bps 4: 9600bps 5: 19200bps |
1 | 3 | |
| 149 | Parity bit | 0: None 1: Odd 2: Even |
1 | 1 | |
| 150 | Stop bit | 1: 1 bit 2: 2 bits |
1 | 1 | |
| 151 | End bit | 0: CR, LF 1: CR |
1 | 0 | |
| 152 | Select INV response mode for specific commands | 0: Enable response 1: No response (enable Error response) 2: No response (disable Error response) |
1 | 0 | |
| 630 631 632 633 634 635 636 637 |
Selection of input terminal DI1 Selection of input terminal DI2 Selection of input terminal DI3 Selection of input terminal DI4 Selection of input terminal DI5 Selection of input terminal DI6 Reserved Reserved |
0: Not used 1: FR 2: RR 3:2DF 4:3DF 5: MBS 6: ES 7: RST 8: AD2 9: Reserved 10: JOG 11: FR+JOG 12: RR+JOG 13: FR+AD2 14: RR+AD2 15,16: Reserved 17: FR+2DF 18: RR+2DF 19: FR+3DF 20: RR+3DF 21: FR+2DF+3DF 22: RR+2DF+3DF 23: FR+AD2+2DF 24: RR+AD2+2DF 25: FR+AD2+3DF 26: RR+AD2+3DF 27: FR+AD2+2DF+3DF 28: RR+AD2+2DF+3DF 29 to 35: Reserved 36: IF 37: 5DF 38: HD 39 to 45 Reserved 46: PID 47 to 64: Reserved 65: 2DF+AD2 66: Reserved 67: 3DF+AD2 68 to 99: Reserved |
1 | 1 2 3 4 5 7 |
|
| 638 | Selection of output terminal DO | 0: Not used 1: In operation 2: Low voltage 3: Reserved 4: In operation 2 5: Frequency matching (1st speed frequency) 6: Frequency matching (1st to 8th speed frequencies) 7: Frequency approach 8: Reserved 9: Electrothermal level signal (Electrothermal 80%) 10: Fin heat prediction signal 11: Reserved 12: Reserved 13: DC braking 14: Lower frequency limit matching 15: Upper frequency limit matching 16: Reserved 17: Reserved 18: FR signal 19: RR signal 20: 2DF signal 21: 3DF signal 22: AD2 signal 23:Reserved 24: JOG signal 25: MBS signal 26: ES signal 27: RST signal 28 to 99:Reserved |
1 | 1 | |
| 641 | Missing phase detection function | 0: Missing input phase detection is invalid,missing output phase detection is invalid. 1: Missing input phase detection is valid, missing output phase detection is invalid. 2: Missing input phase detection is invalid, missing output phase detection is valid. 3: Missing input phase detection is valid, missing output phase detection is valid. |
1 | 2 | |
| 642 | Overvoltage stalling prevention function | 0: Overvoltage stalling prevention function inactive. 1: Overvoltage stalling prevention function active. |
1 | 1 | |
| 643 | Feedback signal break detection time | 0 to 99 99: No function | 0.01 s | 5 |
:The setting cannot be changed during operation.
*1 Typical constants for each model are entered.
*2 to 5 See the following table:
| *2 Cd019 |
*3 Cd020 |
*4 Cd023 |
*5 Cd024 |
|---|---|---|---|
| 5 | 10 | 5 | 10 |