SVC06 Series

Inverter General Specification

| 200V Class | 400V Class 1, 2, 3 | Inverter General Spec | Communication Function Spec |

Control mode Vector control / sensorless vector control /V/f control
performance *1
control range
With PG sensor 0.05Hz-240Hz(1:1000/50Hz reference) *5
Without PG sensor 0.25Hz-240Hz(1:200/50Hz reference) *5
Speed Response/
With PG sensor Response characteristic: 250rad/sec Precision: ±0.01%
Without PG sensor Response characteristic: 100rad/sec Precision: ±0.5%
control range
With PG sensor 1:50(rated torque ratio)
Without PG sensor 1:20(rated torque ratio)
With PG sensor ±10%(of rated torque)
Without PG sensor ±20%(of rated torque)
setting resolution
Digital setting 0.01Hz
Analog setting 0.05%(12bit0-10V,4-20mA), 0.1%(11bit0-5V) of the maximum output frequency
Digital setting ±0.01% of output frequency(at -10-40℃)
Analog setting ±0.2% of the maximum output frequency(at 25℃±10℃) *2
PG input Open collector, push-pull mode (power supply voltage 24V) Max. number of pulses: 491.52kHz *3
DC braking Starting frequency (0.05-20Hz), operation time (0.1-10s), braking force (1-10 grades)
Additional functions Restart after momentary power failure, flying start, multi-speed operation, frequency jump, auto alarm recovery, PID control operation, simple scheduled operation, energy-saving operation and others
Start/stop setting Operation panel, serial communication (RS485, Modbus), control circuit terminals
command setting
Digital setting Operation panel, serial communication (RS485, Modbus), step setting from terminal board
Analog setting 3 channels, 0-5V, 0-10V, 4-20mA, potentiometer (5kΩ, 0.3W and above)
Input signal Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free run stop, alarm reset, emergency stop, jogging selection, step frequency setting, operation signal hold and others
[Digital input: 8 channels (arbitrary allocation)],
[Analog input: 3 channels for current and voltage]
Output signal Contact output Alarm batch and multifunctional contact output (1C contact, 250VAC, 0.3A)
Monitor signal Operating, frequency matching, overload alarm, undervoltge, frequency approach and etc.
[Open-collector output: 3 channels (arbitrary allocation), Analog output: 2 channels]
LED display Frequency, output current, speed, load factor, no unit: (output voltage, power and etc.), operating, alarm
LCD display Various status, code, alarm, message display (English, Japanese, Chinese)
Communication I/F RS485, Modbus-RTU
External power supply output DC24V, 150mA(control terminal board)
Protection function Current limiting, overcurrent shutoff, motor overload, external thermal alarm, undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning function Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
Environment Ambient temperature -10℃-+50℃(no frost):heavy overload, -10℃-+40℃(no frost):light overload
Storage temperature -20℃-+65℃(short-term storage during transportation) *4
Relative humidity 95%RH or less(no condensation)
Elevation 2000m or lower(Decrease the current when higher than 1000m)
Vibration 5.9m/s2(0.6G) or less(JIS C 60068-2-6 standard; IEC60068-2-6)
Gas medium Indoor (no corrosive or inflammable gases, oil mist, or dust)
  • *1 Vary with the environment, condition, motor in use or sensor.
  • *2 The maximum output frequency is at 5V, 10V, and 20mA.
  • *3 An optional board is required for linear driver input.
  • *4 Applicable temperature for medium-term and long-term transportation.
  • *5 When 2-pole motor is set, the maximum value of frequency setting range is 120Hz.