SVC06 Series

400V Class Standard Specifications (2)

| 200V Class | 400V Class 1, 2, 3 | Inverter General Spec | Communication Function Spec |

Item Specification
Model(SVC06-▢▢▢▢ - **4) 0185 0220 0300 0370 0450 0550 0750
Output
specification
Mode A
Heavy overload
Standard applicable motor [kW] 18.5 22 30 37 45 55 75
Rated capacity [kVA] *1 26 32 42 51 62 76 102
Rated current [A] *2 38 46 61 74 90 110 147
Overload current rating *3 150% - 1 min
Output frequency range *4 0.05-599Hz(Starting frequency 0.05-60Hz variable)
Mode B
Light overload
Standard applicable motor [kW] 22 30 37 45 55 75 90
Rated capacity [kVA] *1 31 41 51 62 76 98 120
Rated current [A] *2 46 61 74 90 110 147 173
Overload current rating *3 120% - 1 min
Output frequency range *4 0.05-240Hz(Starting frequency 0.05-60Hz variable)
Rated output voltage *5 3φ 380V-460V
Input
power supply
Voltage & Frequency 3φ 380V-460V , 50/60Hz
Allowable fluctuation Voltage: -15%, +10% Frequency: ±5% Voltage unbalance: within 3%
Power supply impedance 1% and above(Use optional reactor if less than 1%)
Mode A
Heavy overload
Required power capacity [kVA] *6 25.4 30.3 40.4 48.1 58.5 72.4 95.4
Input current [A] *7 With DCL 36.7 43.8 58.3 69.5 84.5 104.5 137.8
Without DCL - - - - - - -
Mode B
Light overload
Required power capacity [kVA] *6 30.3 40.4 48.1 58.5 72.4 95.4 110.5
Input current [A] *7 With DCL 43.8 58.3 69.5 84.5 104.5 137.8 159.5
Without DCL - - - - - - -
Protective structure Totally enclosed(IP20)
Cooling method Forced air cooling
Approximate weight 24kg 38kg 47kg
Carrier frequency Sine wave PWM(carrier frequency 1k-10kHz) *8
DC reactor Standard (Internal)
  • *1 Rated capacity at the output voltage of 400V
  • *2 When input voltage is 400VAC and above, the rated current will be decreased according to the output power
  • *3 One minute is allowed every 10 minutes
  • *4 During vector control, PG sensorless is 0.25Hz-240Hz /PG sensor is 0.05Hz-240Hz (depends on the number of poles)
  • *5 Output voltage cannot exceed power supply voltage
  • *6 Vary with the impedance changes of the power supply including a DC reactor
  • *7 Vary with the impedance of the power supply
  • *8 The maximum value of carrier frequency varies with the inverter capacity mode and operation status.