SVC06 Series

400V Class Standard Specifications (1)

| 200V Class | 400V Class 1, 2, 3 | Inverter General Spec | Communication Function Spec |

Item Specification
Model(SVC06-▢▢▢▢ - **4) 0007 0015 0022 0040 0055 0075 0110 0150
Output
specification
Mode A
Heavy overload
Standard applicable motor [kW] 0.75 1.5 2.2 4 5.5 7.5 11 15
Rated capacity [kVA] *1 1.7 2.8 4.2 6.2 8.7 11.8 17.3 22.2
Rated current [A] *2 2.5 4 6 9 12.6 17 25 32
Overload current rating *3 150% - 1 min
Output frequency range *4 0.05-599Hz(Starting frequency 0.05-60Hz variable)
Mode B
Light overload
Standard applicable motor [kW] 1.5 2.2 4 5.5 7.5 11 15 18.5
Rated capacity [kVA] *1 2.8 4.2 6.2 8.7 11.8 17.3 22.2 26.3
Rated current [A] *2 4 6 9 12.6 17 25 32 38
Overload current rating *3 120% - 1 min
Output frequency range *4 0.05-240Hz(Starting frequency 0.05-60Hz variable)
Rated output voltage *5 3φ 380V-460V
Input
power supply
Voltage & Frequency 3φ 380V-460V , 50/60Hz
Allowable fluctuation Voltage: -15%, +10% Frequency: ±5% Voltage unbalance: within 3%
Power supply impedance 1% and above(Use optional reactor if less than 1%)
Mode A
Heavy overload
Required power capacity [kVA] *6 2.4 3.8 5.8 8.7 12.1 16.4 24.2 31
Input current [A] *7 With DCL 2.1 3.6 5.5 8.2 11.5 15.5 24.5 31.4
Without DCL 3.5 5.6 8.4 12.6 17.6 23.8 35 44.8
Mode B
Light overload
Required power capacity [kVA] *6 3.8 5.8 8.7 12.1 16.4 24.2 31 36.8
Input current [A] *7 With DCL 3.6 5.5 8.2 11.5 15.5 24.5 31.4 37.2
Without DCL 5.6 8.4 12.6 17.6 23.8 35 44.8 53.2
Protective structure Totally enclosed(IP20)
Cooling method Forced air cooling
Approximate weight 4kg 6kg 7kg
Carrier frequency Sine wave PWM(carrier frequency 1k-14kHz) *8
DC reactor Option(External)
  • *1 Rated capacity at the output voltage of 400V
  • *2 When input voltage is 400VAC and above, the rated current will be decreased according to the output power
  • *3 One minute is allowed every 10 minutes
  • *4 During vector control, PG sensorless is 0.25Hz-240Hz /PG sensor is 0.05Hz-240Hz (depends on the number of poles)
  • *5 Output voltage cannot exceed power supply voltage
  • *6 Vary with the impedance changes of the power supply including a DC reactor
  • *7 Vary with the impedance of the power supply
  • *8 The maximum value of carrier frequency varies with the inverter capacity mode and operation status.