SVC06 Series

200V Class Standard Specifications

| 200V Class | 400V Class 1, 2, 3 | Inverter General Spec | Communication Function Spec |

Item Specification
Model(SVC06-▢▢▢▢ - **2) 0015 0037 0075
Output
specification
Mode A
Heavy overload
Standard applicable motor [kW] 1.5 3.7 7.5
Rated capacity [kVA] *1 3.0 6.7 12.6
Rated current [A] 8.0 17.6 33
Overload current rating *2 150% - 1 min
Output frequency range *3 0.05-599Hz(Starting frequency 0.05-60Hz variable)
Mode B
Light overload
Standard applicable motor [kW] 2.2 5.5 11
Rated capacity [kVA] *1 3.7 8.5 16.8
Rated current [A] 9.6 22.3 44
Overload current rating *2 120% - 1 min
Output frequency range *3 0.05-240Hz(Starting frequency 0.05-60Hz variable)
Rated output voltage *4 3φ 200V-220V
Input
power supply
Voltage & Frequency 3φ 200V-230V , 50/60Hz
Allowable fluctuation Voltage: -15%, +10% Frequency: ±5% Voltage unbalance: within 3%
Power supply impedance 1% and above(Use optional reactor if less than 1%)
Mode A
Heavy overload
Required power capacity [kVA]*5 2.6 5.7 11.4
Input current [A]*6 With DCL 6.8 14.9 30
Without DCL 10.4 22.9 46.2
Mode B
Light overload
Required power capacity [kVA]*5 3.1 7.7 16.4
Input current [A]*6 With DCL 8.1 20.3 43.1
Without DCL 12.5 31.2 61.6
Protective structure Totally enclosed(IP20)
Cooling method Forced air cooling
Approximate weight 4kg 7kg
Carrier frequency Sine wave PWM(carrier frequency 1k-14kHz)*7
DC reactor Option(External)
  • *1 Rated capacity at the output voltage of 220V
  • *2 One minute is allowed every 10 minutes
  • *3 During vector control, PG sensorless is 0.25Hz-240Hz /PG sensor is 0.05Hz-240Hz (depends on the number of poles)
  • *4 Output voltage cannot exceed power supply voltage
  • *5 Vary with the impedance changes of the power supply including a DC reactor
  • *6 Vary with the impedance of the power supply
  • *7 The maximum value of carrier frequency varies with the inverter capacity mode and operation status.
Top of page